Basler Electric BE1-11 Modbus Protocol User Manual
Page 85

9424200774 Rev B
79
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
50-6
Mode
SG1
21480
4212*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIMT
50-6
Source
SG1
21482
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-6
Pickup
SG1
21484
4214*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-6
Time Delay
SG1
21486
4216*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-6
Direction
SG1
21488
4218*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-6
Mode
SG2
21490
4220*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIMT
50-6
Source
SG2
21492
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-6
Pickup
SG2
21494
4222*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-6
Time Delay
SG2
21496
4224*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-6
Direction
SG2
21498
4226*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-6
Mode
SG3
21500
4228*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIMT
50-6
Source
SG3
21502
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-6
Pickup
SG3
21504
4230*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-6
Time Delay
SG3
21506
4232*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-6
Direction
SG3
21508
4234*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
51-1
Mode
SG0
21510
4236*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
51-1
Source
SG0
21512
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
51-1
Pickup
SG0
21514
4238*
Float
4
R W
Amp
0.5 - 16
FGIMT
51-1
Curve Index
SG0
21516
4240*
Uint32
4
R W
n/a
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28
FGIMT
51-1
Direction
SG0
21518
4242*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT