Basler Electric BE1-11 Modbus Protocol User Manual
Page 70

64
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
27X-1
Time Delay
SG2
20608
3538*
Float
4
R W
Millisecond 50 - 600000
FGIT
27X-1
Inhibit Level
SG2
20610
3540*
Float
4
R W
Volt
1 - 150
FGIT
27X-1
Time Multiplier
SG2
20612
3542*
Float
4
R W
n/a
0 - 9.9
FGIT
27X-1
Mode
SG3
20614
3544*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3
rd
Harmonic=5
FGIT
Reserved
20616-
19
27X-1
Timing Mode
SG3
20620
3546*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIT
27X-1
Pickup
SG3
20622
3548*
Float
4
R W
Volt
1 - 150
FGIT
27X-1
Time Delay
SG3
20624
3550*
Float
4
R W
Millisecond 50 - 600000
FGIT
27X-1
Inhibit Level
SG3
20626
3552*
Float
4
R W
Volt
1 - 150
FGIT
27X-1
Time Multiplier
SG3
20628
3554*
Float
4
R W
n/a
0 - 9.9
FGIT
27X-2
Mode
SG0
20630
3556*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3
rd
Harmonic=5
FGIT
Reserved
20632-
35
27X-2
Timing Mode
SG0
20636
3558*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIT
27X-2
Pickup
SG0
20638
3560*
Float
4
R W
Volt
1 - 150
FGIT
27X-2
Time Delay
SG0
20640
3562*
Float
4
R W
Millisecond 50 - 600000
FGIT
27X-2
Inhibit Level
SG0
20642
3564*
Float
4
R W
Volt
1 - 150
FGIT
27X-2
Time Multiplier
SG0
20644
3566*
Float
4
R W
n/a
0 - 9.9
FGIT
27X-2
Mode
SG1
20646
3568*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3
rd
Harmonic=5
FGIT
Reserved
20648-
51
27X-2
Timing Mode
SG1
20652
3570*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIT
27X-2
Pickup
SG1
20654
3572*
Float
4
R W
Volt
1 - 150
FGIT
27X-2
Time Delay
SG1
20656
3574*
Float
4
R W
Millisecond 50 - 600000
FGIT
27X-2
Inhibit Level
SG1
20658
3576*
Float
4
R W
Volt
1 - 150
FGIT
27X-2
Time Multiplier
SG1
20660
3578*
Float
4
R W
n/a
0 - 9.9
FGIT
27X-2
Mode
SG2
20662
3580*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3
rd
Harmonic=5
FGIT
Reserved
20664-
67
27X-2
Timing Mode
SG2
20668
3582*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIT
27X-2
Pickup
SG2
20670
3584*
Float
4
R W
Volt
1 - 150
FGIT
27X-2
Time Delay
SG2
20672
3586*
Float
4
R W
Millisecond 50 - 600000
FGIT
27X-2
Inhibit Level
SG2
20674
3588*
Float
4
R W
Volt
1 - 150
FGIT
27X-2
Time Multiplier
SG2
20676
3590*
Float
4
R W
n/a
0 - 9.9
FGIT