System installation, 1 overview, 2 before installation – Artesyn Centellis 2000 Shelf Release 3.0 Installation and Use (May 2014) User Manual
Page 83: 1 type label location, 2 requirements, 1 overview 3.2 before installation, 1 type label location 3.2.2 requirements, Chapter 3

Chapter 3
Centellis 2000 Shelf Release 3.0 Installation and Use (6806800L99G)
83
System Installation
3.1
Overview
The following sections help you to start up and maintain the system:
3.2
Before Installation
This section provides the following information:
Type label location
Requirements
Tools you will need
Required torque values
3.2.1
Type Label Location
The serial number label for the shelf is located at the system’s right hand side.
3.2.2
Requirements
Please ensure that the requirements outlined in section
are met.
To maintain the maximum power rating of the Centellis 2000 AC, the power input cables must
have a minimum cross section of 1 mm
2
.
To maintain the maximum power rating of the Centellis 2000 DC, the power input cables must
have a minimum cross section of 2.5 mm
2
, AWG 12.
Step
Description
This section provides information about the requirements,
unpacking and inspecting the delivery and the type label
location.
This section provides information about how to mount the
system into a rack and how to ground the system.
This section provides information on how to power down the
system and remove it from a rack.