beautypg.com

1 ac psu input power requirements, Table 7-1, Ac psu input power requirements – Artesyn Centellis 2000 Shelf Release 3.0 Installation and Use (May 2014) User Manual

Page 144: Power subsystem

background image

Power Subsystem

Centellis 2000 Shelf Release 3.0 Installation and Use (6806800L99G)

144

7.2.4.1

AC PSU Input Power Requirements

The following table lists the PSU input power requirements:

Table 7-1 AC PSU Input Power Requirements

Feature

Value

Input Voltage Range

90 VAC to 254 VAC (Universal Input)

Input Nominal Line
Voltages

100 VAC to 240 VAC, 50 Hz to 60 Hz

Frequency Range

47 Hz to 63 Hz

Leakage Current

Maximum of 3.5 mA

Power Factor

Minimum of 0.98 at full load and nominal line

Harmonic Content

As per EN61000-3-2, 1995 Version, Sections 5 and 7

Efficiency

Better than 85% at nominal line and load between 50 and 100%

Better than 80% across the operation voltage range, at loads
between 50 and 100%

In Rush Current

At insertion of a PSU with AC voltage available at the hot-plug
connector, the charging of input capacitance or converter startup
current shall not lead to arcing or any damage of the hot-plug
connector pin’s (see also 4.2.16 hot-swap operation)

Isolation

Primary-secondary and primary to ground (PE) isolation shall
follow EN60950 and harmonized international applicable
standards.

AC PSU input is fused at 16A. External wiring and circuit interruption should be sized
accordingly.