Table 2-3 AC System Power Requirements

Feature

Value (For AC)

Rated voltage and input current

100 VAC to 240 VAC and 8.5 A Max

Operating voltage range

90 VAC to 254 VAC

Table 2-4 DC System Power Requirements

Feature Value

Rated voltage and input current

-48 VDC to -60 VDC, 18 A to 15 A
US and Canada: -48 VDC, 18 A

Operating voltage range

-40.0 VDC to -72 VDC
US and Canada: -40.0 VDC to -60 VDC

Maximum power dissipation

The power distribution is tested for
supplying 320 W/front slot to all slots
simultaneously and additionally 35
W/rear slot.

User card power requirement

max. 8W

When installing additional blades or modules, make sure that the power consumption of all
installed modules does not exceed the system's maximum power dissipation.