CIRCUTOR PowerStudio Series User Manual
Page 89

PowerStudio
User Manual 89
• Voltage transformation ratio: Primary and secondary voltage programming. The product
between the primary value and the primary current must be the same as or less than
20,000,000. The primary value, depending on fullscale, must be between 1 and the value of
the following table:
Full-scale
Maximum value.
110v
99.999
275v
70.000
300v
70.000
500v
40.000
• Current transformation ratio: This is the device primary current value. Value may be
between 1 and 10,000 A. The secondary current is 5A in the CVM-144.
This section shows the configuration of the device analogue outputs, and the option is given to
configure them with the desired values.
• Variable: Permits any parameter measured by the CVM-144 to be selected, except
parameters corresponding to energy.
• Full scale: Value of the parameter to which the zero of the scale is assigned.
• Full scale: Value of the parameter to which the maximum value of the scale is assigned.
• Type: Output type, allows outputs 0 – 20 mA, 4 – 20 mA or 0 – 10 V to be chosen, depending
on the device.
• Variable: This indicates the name associated with the analogue input.
• Units: This indicates the type of units the variable represents.
• Full scale: Value of the parameter to which the zero of the scale is assigned.
• Full scale: Value of the parameter to which the maximum value of the scale is assigned.
• Type: Input type, allows inputs of 0 – 20 mA, 4 – 20 mA or 0 – 10 V to be chosen, depending
on the device.
• Decimal point: Position of the decimal point. Only if the device allows us to display the
analogue inputs with real measurement values.