Depending on the device connected, some fields will be disabled.
Displays general information.Among other parameters the current connection configuration
may be seen.
• Voltage transformation ratio: Primary and secondary voltage programming. The product of
the primary value and the primary current must be the same as or less than 20,000,000.
• Current transformation ratio: This is the device primary current value. Value may be
between 1 and 30,000 A. The secondary current is 1A or 5A.
• Capacitor power measure transformation ratio : The primary capacitor current measure
value may be between 1A and 999A. The secondary capacitor current measure value may be
between 1A and 5A.
Machine connection and registration times. For the TF, TF-C and TF-CDI models the units are
cycles, for the rest of models the units are seconds.
Configuration of the inductive phi or capacitative cosine.
Clicking the button resets the device energy counters to zero.
Clicking the button sends the PC's time of day to the machine.