14 event variables, Event variables – CIRCUTOR PowerStudio Series User Manual
Page 290
PowerStudio PowerStudio
290 User Manual
The device communicates correctly, but it detects that some of the phases are poorly connected.
130
The version of the device is incompatible with the software.
258
The SD Memory Card is invalid, write-protected or not present.
514
2.1.14 Event Variables
The event variables will be coded for use in formulas and expressions such as
R$EVE_variable. name
Using the R$EVE prefix tells the program this is an event variable rather than a device variable.
The following is a table with the different variables associated with each event
Identifier
Description
ST
Event status (0:disabled, 1:Enabled)
TACT
Time the event has been active, the value is 0 when the event is disabled
CACT
1
Counter of the number of activations
CDIS
1
Counter of the number of deactivations
CACK
1 2
Counter of the number of recognitions
CTIM
1
% Of consultation period time that the incident is enabled
1
Only if the event is recorded in a file
2
Only if the incident is reported
10
Only in SCADA and Deluxe versions