PowerStudio
User Manual 287
RCPD
RCTD
RCPM
RCTM
RGU-10 RA
X
X
X
X
Pre-alarm trigger output status
Value
Not enabled
0
Enabled
1
Locking output status
Value
Not locked
0
Locked
1
Coil trigger output status
Value
Not Tripped
0
Tripped
1
Status of the device
Value
Start
0
Rest
1
Earth differential trigger locking
2
Earth differential trigger waiting
3
Circuit breaking trigger locking
4
Circuit breaking trigger waiting
5
Toroid disconnected
6
External input enabled
7
Remote trigger
8
Test trigger
9
Manufacturing mode
10
Calibration mode
11
To carry out a channel reset on the RGU-10 devices the RST variable must be forced to value 0.
To carry out a remote triggering of the channel the RST variable should be forced to the value 1.
2.1.11.15 RRM-C
Reconection counter
No. of reconnections selected
Time between
reconnections
Device status
RC
RN
RT
ST
RRM-C
X
X
X
X
Device status
Value
Unknown
65535
Connected
0
Locked
1
External trigger
2
Residual current device trigger
4
Communication trigger
8
External and communication trigger
10
On RRM-C devices the device status can be forced to 16 to reset it, or to 17 trigger the device
externally.
2.1.11.16 TAGREADER
Tag
TAG
Time
TIME