PowerStudio
User Manual 59
1. Channel status:
•
Status ON.
•
Pre-alarm status.
•
Status OFF.
2. Relay status:
• ON. Unlocked channel.
• OFF. Locked channel.
3. Channel operating mode:
•
Differential mode.
•
Relay mode.
4. Additional information on the status of the channel:
• Pre-alarm: Pre-alarm enabled.
• Reconnection: Channel disconnected with timed reconnection process.
• Remote: Channel disconnected by external triggering, cannot be automatically
reconnected.
5. Additional channel information:
• Reconnection enabled: Reports that channel reconnections have been enabled. Only
if the channel is in differential mode.
• Channel can be locked. Reports that the channel will remain locked when trigged, with
manual or remote reset being necessary. Only if the channel is in relay mode.
6. Reset button. If the channel is triggered, the button will remain disabled. Push the button to
restart the channel.
7. OFF button. External disconnection of the channel. The button will remain disabled if the
channel has not been triggered.
8. Adjustment button. Enables programming of sensitivity and channel delay. Channel
information is also shown.
9. Channel instantaneous differential current value. When the channel Instantaneous differential
current value exceeds the limits of the value bar, either in excess or default, this will be
indicated as shown in the figure (arrow below the value).
10. Channel trip threshold value configured.
11. Channel pre-alarm value configured.
12. Differential current value detected when the channel triggers.