CIRCUTOR PowerStudio Series User Manual
Page 155
PowerStudio
User Manual 155
Configuration of the transformation ratio of the device.
• Voltage transformation ratio: Primary and secondary voltage programming. The product
between the primary value and the primary current must be the same as or less than
20.000.000. The primary value must be between 1 and 999.999 V while the secondary can be
between 1 and 999 V.
• Current transformation ratio: This is the primary and secondary current value the device
has. The primary can value between 1 and 9999 A and the secondary between 1 or 5 A.
Device screen display
• Omit reactive measurement: The reactive measurements are not shown on the device
screen, although they will continue to be displayed on the software display screens.
• Omit partial counters: Partial counter measurements are not shown on the screen of the
device nor on the display screens of the software.
Configuration of the "backlight" disconnection. The value should oscillate between 0 and 10 seconds.
On clicking the button all the partial counters of the device will be started.
Configuration of the number of quadrants. With only 2 quadrants the consumed energy counters will be
taken into consideration and with 4 the consumed and generated energy counters.
Configuration of the output relay of the active energy. The number of Wh equivalent to an output
impulse and the variable that will be measured to give this pulse. If the pulse value is 0, the output will
be treated like a standard digital output, enabling it value to be forced from 0 to 1.