BINDER KB 23 User Manual
Page 47

KB (E3.1 + E5.1) 11/2014
page 47/100
Normal Display
Display 1 shows
e.g. 19.8
(actual temperature value)
Display 2 shows e.g. 15.05.06 13:52 - -
(actual date and time, actual switching state of week
program timer channel 1: Off, channel 2: Off)
Press down key
for 5 sec
Display 1 shows
e.g. 0000
Display 2 shows PROGRAM EDITOR
(you are in the program editor)
Press down key
for 5 sec
Display 1 shows
0000
Menu visible only if week program timer is activated.
Display 2 shows WEEK PROG. EDITOR
(you are in the week program editor)
Press down key
for 5 sec
Display 1 shows
0000
Display 2 shows
USER – LEVEL
(you are in the user level)
Press program key
Display 1 shows
0000
Display 2 shows UserCod?
0000
(enter user code, display flashes)
Enter the user code using arrow keys
e.g.
0001 (basic setting,
or the valid code in case it has been previously
changed in this menu).
Value is shown in both displays.
Automatically forward after 2 sec
Display 1 shows
1
(actual address: 1)
Display 2 shows
Adress
1
(entry of unit address)
(actual address: 1)
Enter the unit address (1 up to 254)
using arrow keys
Address is shown in both displays.
Press key
Display 1 shows
1
(actually valid user code: 1)
Display 2 shows
User-cod
1
(change user code)
(actually set: 1)
Enter a new value using arrow keys
Value is shown in both displays.
Press key
Display 1 shows
0000
(no function)
Display 2 shows
Saf.mode: Limit
(select set-point mode of safety controller)
(actual setting: “limit”)
Select between “Limit” and “Offset” using
arrow keys
Setting is shown in display 2.
Press key
Display 1 shows
e.g. 65
(actual setting: 65 °C / 149°F)
Display 2 shows
Saf.setp
65
(temperature value of over temperature safety device)
(actual value: 65 °C / 149°F)
Enter a new value using arrow keys
Value is shown in both displays.