SAFE OPERATION
}
Safe operation after at least one safety function has been activated
}
Transition to STO: Internal error
}
Transition to SS1 due to
–
Error
–
Violation of limit values
–
Demand upon safety function SS1
}
Transition to NORMAL OPERATION: No safety function activated
SS1
}
SS1 is activated
–
After violation of the limit values
–
After an error
–
After a demand upon safety function SS1
}
Transition to STO: After activation of SS1 (drive is brought to a standstill with a defined
braking ramp)
STO
}
There is no power to the motor after execution of safety function STO
}
Transition to CONFIG: Demand upon the Configurator
}
Transition to NORMAL OPERATION due to
–
Reset of safety card (see "Recommissioning")
–
Prior POWER ON
8.2
Testing the safe pulse disabler
The safety card meets the requirements of EN IEC 61508 up to SIL 3 and EN ISO 138491
up to PL e.
To achieve category SIL 3 or PL e, the operator must ensure that the function of the safe
pulse disabler is tested periodically, after 8 hours at the latest, by triggering safety functions
SS1 or STO:
}
By restarting after safety functions SS1 or STO have been triggered as a condition of
operation
or
}
By restarting after safety function SS1 has been triggered by the operator
To test the safe pulse disabler, proceed as follows:
1. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 0 V
}
The safety card performs the safety function SS1 (Safe Stop 1) and switches to a
"STOP" condition. The "STO" LED flashes.
2. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 24 V.
}
The safety card switches to a "STARTUP" condition. The device and the safe pulse dis
abler are tested. The "RUN" LED flashes.
}
The safety card switches to a "RUN" condition. The "RUN" LED is lit continuously.
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1-2 PMCprotego S1-2-C