5 reaction times, Reaction times – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual
Page 54
![background image](https://www.manualsdir.com/files/762795/content/doc054.png)
Function description
Operating Manual PMCprotego S12(C)
1002528EN02
54
INFORMATION
Further information on the command can be found in the servo amplifier's
online help, on the "Motion Control" CD (file ascii_dd5protego.chm).
Please also refer to the operating instructions for the servo amplifier.
4.5
Reaction times
The reaction times refer exclusively to the inputs and outputs on a servo amplifier with
safety card when:
}
The signal at the inputs changes
}
The limit value is exceeded
}
Internal errors are present
To determine the overall reaction times, the corresponding internal processing times in the
servo amplifier, bus systems, periphery devices and controllers must also be taken into ac
count.
Processing time of the digital input
The response and error reaction time takes into account the following processing times:
}
Processing time of digital input T
IN
: The time it takes for a "0" or "1" signal in the safety
card to be detected once a signal has changed at the input. The processing time takes
into account the input filter time, temperature drift, spread of components, etc.
}
Internal processing times of the safety card
–
T
CYCLE
: Scan time of the safety card's processor system
–
T
OUT
: Processing time for the safety card's shutdown path
}
T
PULSE
: Processing time for the safe pulse disabler in the servo amplifier
Response time:
}
The time it takes for the shutdown signal to be provided for the servo amplifier's power
element, once a signal has changed at the input
T
IN
+ T
CYCLE
+ T
OUT
+ T
PULSE
Error reaction time:
}
The time it takes for the shutdown signal to be provided for the servo amplifier's power
element, once a limit value has been exceeded or an internal error has occurred.
T
CYCLE
+ T
OUT
+ T
PULSE
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1-2 PMCprotego S1-2-C