Function description
Operating Manual PMCprotego S12(C)
1002528EN02
21
}
STO is only activated directly when
–
there is an internal error on the servo amplifier or safety card
–
the STO delay time is set to 0
–
the inputs "SS1 Activate" and "SS1 SIL3/Reset" simultaneously switch to a "0" sig
nal
}
The STOENABLE reset lock on the servo amplifier has no function if the servo ampli
fier contains a safety card. The output contact is linked internally. In this case, the
safety card activates the safe pulse disabler on the servo amplifier in order to shut
down the power element.
}
The safety function "Safe Torque Off" corresponds to a category 0 stop (uncontrolled
stop) in accordance with EN 602041.
Prerequisites for normal operation:
}
Input "SS1 Activate" and "SS1 SIL3/Reset": "1" Signal (+24 VDC)
}
"Ready" output: "1" Signal (+24 VDC). The safety card is ready for operation.
}
"STO Acknowledge" output: “0” Signal
}
To achieve SIL3 or PL e: Connect the output "STO SIL3" to servo amplifier terminal
X4A/ 3.
Safety function is activated
}
By an error after limit values have been exceeded or
}
By an internal error on the safety card or servo amplifier, if the drive can no longer be
braked safely
}
By executing the safety function SS1 (1/0 pulse edge). In this case the drive is braked
safely before it is switched to torquefree (see section: "Safe stop – SS1").
}
The inputs "SS1 Activate" and "SS1 SIL3/Reset" simultaneously switch to a "0" signal
}
A second error occurs while SS1 (drive shutdown) is activated.
Reaction:
}
The drive is switched to torquefree
}
"STO Acknowledge" output: “1” Signal
If any external forces influence the motor axis (e.g. suspended loads), additional measures
(e.g. a safety holding brake) are required in order to eliminate hazards.
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1-2 PMCprotego S1-2-C