Braking ramp in normal operation
The drive starts with the configured braking ramp when safety function SS1 has been
activated. Once the time has elapsed, STO is activated.
}
ESTOP braking ramp:
The drive starts with the configured braking ramp when
–
there is an internal error
–
limit values are exceeded
}
Safety function STO is activated when
–
the actual braking period is longer than the configured STO delay time.
–
the configured limit value for the position error is exceeded.
–
another error occurs while SS1 is activated
–
the STO delay time has elapsed
}
Automatic STO at standstill
A standstill threshold for activating the safety function STO can be specified in the Con
figurator.
Safety function STO is activated when
–
standstill is achieved while the STO delay time is running.
–
the STO delay time has elapsed.
Input and output assignment
}
Input
–
X30/1: SS1 Activate
}
Outputs
–
X30/5: STO Acknowledge
–
X30/16: Ready
Prerequisites for normal operation:
}
Input "SS1 Activate" and "SS1 SIL3/Reset": "1" Signal (+24 VDC)
}
"Ready" output: "1" Signal (+24 VDC). The safety card is ready for operation.
}
"STO Acknowledge" output: “0” Signal
}
To achieve SIL3 or PL e: Connect the output "STO SIL3" to servo amplifier terminal
X4A/ 3.
The safety function is activated via
}
1/0 pulse edge at the input "SS1 Activate"
or
}
1/0 pulse edge at the input "SS1 SIL3/Reset"
}
Internal error
Signal status of the inputs "SS1 Activate" and "SS1 SIL3/Reset"
}
The STO delay time starts when one of the two inputs "SS1 Activate" or "SS1 SIL3/Re
set" is set to "0". The safety function "STO" is activated once the STO delay time has
elapsed.
}
The safety function "STO" is activated immediately if the second input is also set to "0".
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1-2 PMCprotego S1-2-C