Operation

Operating Manual PMCprotego S1­2(­C)
1002528­EN­02

81

8

Operation

Prerequisites for normal operation are:

}

Commissioning is complete

}

The safety card contains the configuration data

}

The safety functions have been tested

}

The "RUN" LED is lit

During operation

}

Any pulse edge change at the safety card's safe inputs is monitored

}

The safety functions are performed in accordance with the configuration.

8.1

Operating states

The safety card is always in clearly defined operating states.

NORMAL

OPERATION

CONFIG

SAFE

OPERATION

SS1

STO

POWER ON

Download
configuration

Safety
function
deactivated

Safety
function
activated

Demand
upon
Configurator

Internal error

Error

STO

Limit values
Error
SS1 Activate

Error

Reset

POWER ON

}

The supply voltages are present.

}

Transition to STO once the supply voltages are applied

CONFIG

}

Download of configuration to the safety card

}

Transition to state of NORMAL OPERATION: Configuration downloaded without error

}

Transition to state of STO: Incorrect configuration data

}

The motor is switched volt free in the CONFIG operating state (STO is active)

NORMAL OPERATION

}

No safety function activated

}

Transition to state of STO: Internal error

}

Transition to SAFE OPERATION: A safety function is activated