Function description

Operating Manual PMCprotego S1­2(­C)
1002528­EN­02

16

NOTICE

Inputs "SS1 Activate" and "SS1 SIL3/Reset" must always be connected.

In the case of all inputs, only tested outputs from a safety control system
may be connected.

4.2.2

Outputs

4.2.2.1

Single­pole outputs

Safe, single­pole outputs signal the status of the activated safety functions and the safety
card's state of readiness.

Outputs with fixed assignment:

}

STO Acknowledge

1: Power element switched off

– Internal error on servo amplifier or safety card

– Limit values exceeded

– Activated via SS1

0: Drive in closed loop operation

}

STO SIL3

1: Second shutdown route on

0: Second shutdown route off

}

Ready

1: Safety card is ready for operation

0: Safety card is not ready for operation. Possible causes:

– Safety card is starting up

– No supply voltage

– Major internal error

– Error on the feedback output "STO Acknowledge"

INFORMATION

"Ready" is a second feedback channel for the safety function STO. The
"Ready" output switches off if a problem occurs at the feedback signal "STO
Acknowledge".