2 recommissioning after error, Recommissioning after error – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual
Page 73
![background image](https://www.manualsdir.com/files/762795/content/doc073.png)
Commissioning
Operating Manual PMCprotego S12(C)
1002528EN02
73
Key:
}
Servo amplifiers
–
24 V: Supply voltage
–
BTB/RTO: Relay contact for operational readiness, servo amplifier
–
L1, L2, L3: Mains voltage
–
X8: Intermediate circuit
–
STOENABLE: Start interlock
–
HW/SWEnable: Hardware and software enable
–
Enable U, V, W: Motor connection
–
Motor n: Motor speed
–
t
1
: Servo amplifier's runup time
–
t
2
: Load time, intermediate circuit capacitance
–
t4: Processing time until servo amplifier is enabled
}
Safety card
–
24 V: Supply voltage
–
SS1 Activate: SS1 activated
–
SS1 SIL3/Reset: Input for SIL3 and reset
–
Ready: Operational readiness
–
STO Acknowledge: Status: STO activated
–
t3: Safety card's runup time
7.3.2
Recommissioning after error
This section describes the recommissioning process after an error has occurred.
Rectify the error, noting:
}
The error messages in the error stack
}
The LED display.
Perform a reset as follows:
}
Switch inputs "SS1 Activate" or "SS1 SIL3/Reset"
or
}
Run the command "CLRFAULT"
7.3.2.1
Switching the inputs "SS1 Activate" or "SS1 SIL3/Reset"
1. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 0 V
}
The safety card performs the safety function SS1 (Safe Stop 1) and switches to a
"STOP" condition. The "STO" LED flashes.
2. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 24 V.
}
The safety card switches to a "STARTUP" condition. The device and the safe pulse dis
abler are tested. The "RUN" LED flashes.
}
The safety card switches to a "RUN" condition. The "RUN" LED is lit continuously.
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1-2 PMCprotego S1-2-C