Wiring

Operating Manual PMCprotego S1­2(­C)
1002528­EN­02

58

6

Wiring

6.1

General wiring guidelines

Inputs

}

Appropriate wiring must be used to exclude short circuits between the inputs or to a
supply line!

}

Signal lines must be shielded.

Outputs

}

If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load.

Possible remedy: Exclude the error by using separate multicore cable for supply
voltages

}

Use appropriate wiring to exclude short circuits between the outputs!

}

Signal lines must be shielded.

}

The outputs do not need suppression for inductive loads.

Cable material

}

Use copper wiring.

Please note:

}

Cable cross sections for field connection terminals in mm

2

:

Digital inputs/outputs, supply voltage: 0.5 (AWG20) ... 1.0 (AWG18), AEH without
plastic collar, in accordance with DIN 46228/1

}

Max. cable lengths

Supply voltage: Max. 30 m

Digital inputs and outputs: Max. 30 m