7.2
Messages
7
Operation
7.2.1.6
Error stack on the LC display
Error stack on the LC display
7-
Betrieb_Display_erweiterte_Diagnose
The error stack can be read from the PNOZmulti Configurator or shown
on the LC display. The error stack helps Pilz technical support with fault
diagnostics. The error stack can store up to 64 status and error messag-
es.
The following information is shown on the LC display:
Sequential number of an error stack entry. A new error stack entry is
stored in first place.
Error class (EC) and error information (EI)
Error number (EN) and five error parameters (PA)
Procedure for displaying the error stack on the LC display:
Use the rotary knob to display the error stack.
Procedure for reading the error stack with the PNOZmulti Configurator:
See online help for the PNOZmulti Configurator
INFORMATION
Use the rotary knob to exit the error stack.
01/64
EN: 01
EC: 02
FF 00 00 00
EI: 12
PA: 09
PNOZ mm0p
CRC: 0x8108
project
09.02.2009
H 00000000003
HW 0x07
SW 0x0000
SN 0x000000006
Show
error stack?
X3
X1
X2
X4
T T