Control cabinet installation, 1 dimensions, 5installation – Pilz PNOZ mm0.2p User Manual

Page 23: 3 control cabinet installation

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

5-3

5.3

Control cabinet installation

5

Installation

5.3

Control cabinet installation

5300

Control cabinet installation

5-

Montage_multi_mini_allgemein

The unit should be installed in a control cabinet with a protection type

of at least IP54.

Fit the safety system to a horizontal mounting rail. The venting slots

must face upwards and downwards. Other mounting positions could

destroy the safety system.

Use the notch on the rear of the unit to attach it to a mounting rail.

In environments exposed to heavy vibration, the unit should be se-

cured using a fixing element (e.g. retaining bracket or end angle).

Push the unit upwards or downwards before lifting it from the mount-

ing rail.

To comply with EMC requirements, the mounting rail must have a low

impedance connection to the control cabinet housing.

Montage_multi_mini_Temperatur

The ambient temperature of the PNOZmulti units in the control cabi-

net must not exceed the figure stated in the technical details, other-

wise air conditioning will be required.

Montage_EMV ESD

5.3.1

Dimensions

Dimensions

5-

Abmessungen PNOZ mm0.2p

* with spring-loaded terminals

CAUTION!
Damage due to electrostatic discharge!

Electrostatic discharge can damage components. Ensure

against discharge before touching the product, e.g. by touching

an earthed, conductive surface or by wearing an earthed arm-

band.

120 (4.72")

* 100 (3,94")

98 (3.86")

45

(1.77")

58,81 (2.31"

15,15 (0.6")