6 commissioning, General wiring guidelines, 6commissioning – Pilz PNOZ mm0.2p User Manual

Page 25: 1 general wiring guidelines

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-1

6.1

General wiring guidelines

6

Commissioning

6

6000

Commissioning

Commissioning

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

Verdrahtung_mini_multi_HL_Ausg

The wiring is defined in the circuit diagram in the Configurator. There you

can select the inputs that are to perform a safety function and the out-

puts that are to switch this safety function.

Note:

Information given in the "Technical details" must be followed.

Outputs O0 to O3 are semiconductor outputs

Use copper wire that can withstand 75 °C.

Sufficient fuse protection must be provided on all output contacts

with inductive loads.

The safety system and input circuits must always be supplied by a

single power supply. The power supply must meet the regulations for

extra low voltages with safe separation.

Test pulse outputs must exclusively be used to test the inputs. They

must not be used to drive loads.

Do not route the test pulse lines together with actuator cables within

an unprotected multicore cable.

Verdrahtung_multi_Basis_Schaltmatte

Test pulse outputs are also used to supply safety mats that trigger a

short circuit.

Test pulses that are used for the safety mat may not be reused for

other purposes.

Verdrahtung_multi_Verbindungsschnittstelle

When connecting two base units via the integrated interface please

note:

The max. cable length between two base units on a connection with

– one link module PNOZ ml1p

– one link module PNOZ ml1p from V2.0, PNOZ mml1p or one base

unit PNOZ mm0.2p: 1000 m

Connect the inputs and outputs via the two interfaces using 4-core

shielded cable. The cables must be twisted in pairs (see “Preparing

for operation”).

Note the crossover cabling, e.g. CA+ with CB+.

The cables must be classified into a minimum of Category 5 in ac-

cordance with ISO/IEC 11801.