4 diagnostics, 4function description, 1 device properties – Pilz PNOZ mm0.2p User Manual
Page 20
4.1
Device properties
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-4
Input delay and switch-off delay are only included once in the reaction
time. The data transmission time is multiplied by the number of con-
nections.
Please refer to the connection examples under "Preparing for opera-
tion".
Virtual inputs and outputs:
Inputs and outputs for both PNOZmulti systems are assigned in the
PNOZmulti Configurator. Inputs and outputs with the same number are
assigned to each other, e.g. output o5 on one PNOZmulti system to in-
put i5 on the other PNOZmulti system.
Funktionen_multi_Verbindungsmodul_l1p_Bild
4.1.2.4
Diagnostics
Diagnostics
4-
Funktionen_mini_multi_Basis_Diagnose
The status and error messages displayed by the LEDs are saved in an
error stack. This error stack can be shown on the display or can be read
from the PNOZmulti Configurator via the USB port.
CAUTION!
For signals that are forwarded or received via the link module or
interface, the overall reaction time, e.g. the maximum reaction
time of the series connection of n base units, must always be
considered in the risk assessment.
The risk assessment must consider all hazards as regards the
reaction time and the safety distance. The overall reaction time
must not delay the arrival of a safe condition by more than the
permitted time.
Base unit 1
Virtual outputs
o0
...
o31
Virtual inputs
i0
...
i31
Base unit 2
Virtual inputs
i0
...
i31
Virtual outputs
o0
...
o31