beautypg.com

Messages, 1 display elements, 1 status indicators – Pilz PNOZ mm0.2p User Manual

Page 38: 2 display elements for device diagnostics, 7operation, 2 messages

background image

7.2

Messages

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-2

7.2

Messages

7200

Messages

7-

Betrieb_Meldungen_Basis_BA

The PNOZmulti control system is ready for operation when the "POW-

ER" and "RUN" LEDs on the base unit are lit continuously.

7.2.1

Display elements

Display elements

7-

7.2.1.1

Status indicators

Status indicators

7-

Anzeige Legende 3x

Legend:

7.2.1.2

Display elements for device diagnostics

Display elements for device diagnostics

7-

Betrieb_Anzeige_mini_multi_Basis_BA

LED on

LED flashes

LED off

Basic

Errors

RUN

DIAG

FAULT

IFA

U

LT

OFAULT

The existing user program has been deleted.

External error on the base unit, leading to a safe condition, e.g. chip card not in-
serted

External error on the outputs of the base unit, e.g. short across the contacts, lead-
ing to a safe condition.

Internal error on the base unit

Internal error on the base unit (inputs)

Internal error on the base unit (outputs)

Base unit in a STOP condition

External error on the inputs of the base unit, which does not lead to a safe condi-
tion, e.g. partially operated.

External error on the outputs of the base unit, which does not lead to a safe condi-
tion, e.g. feedback input defective.

The fieldbus module has not been recognised.
Or
The base unit was identified by the PNOZmulti Configurator via the Ethernet inter-
face.
Or
An existing fieldbus connection was interrupted.