3 chip card, 2overview, 1 unit structure – Pilz PNOZ mm0.2p User Manual
Page 10
2.1
Unit structure
2
Overview
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
2-2
Display for:
– Error messages
– State of supply voltage
– State of inputs/outputs
– Status information
– Unit information
Monitors shorts across the inputs through test pulse outputs
Monitoring of shorts between the safety outputs
Plug-in connection terminals:
either spring-loaded terminal or screw terminal available as an acces-
sory (see order reference)
Rotary knob for menu control
Gerätemerkmal_multi_Mini_Basis_Anschluss_Erweiterung
Expansion modules can be connected
(please refer to the document "PNOZmulti System Expansion" for de-
tails of the type and number that can be connected)
Gerätemerkmal_multi_Mini_Basis_integr_Verbindungsschnittstelle
Integrated interface (RJ45 socket) for safe connection of two config-
urable control systems:
– Connection options:
- Two PNOZmulti Mini base units
or
- One PNOZmulti Mini base unit with one PNOZmulti base unit
(both the units to be connected need either an integrated interface
or a link module)
– Point-to-point connection via 4-core shielded, twisted-pair cable
– 32 virtual inputs and 32 virtual outputs for data transfer
2.1.3
Chip card
Chip card
2-
Bestimmung/Gertebeschreibung_multi_Chipkarte
To be able to use the product you will need a chip card.
Chip cards are available with memories of 8 kByte and 32 kByte. For
large-scale projects we recommend the 32 kByte chip card (see Tech-
nical Catalogue). Accessories chapter).