TROUBLESHOOTING (cont)
TROUBLE/SYMPTOM
PROBABLE CAUSE
REMEDY
Low oil pressure, (cont)
Clogged oil line.
Remove obstruction.
Worn oil pump.
Replace pump assembly.
Worn compressor bearings.
Replace.
Cold compressor.
Liquid carryover from evaporator.
Check refrigerant charge and expansion
valves.
Low crankcase oil level.
Oil return check valve stuck closed.
Repair or replace check valve.
Cylinders and crankcase
sweating.
Refrigerant floodback.
Check refrigerant charge and expansion
valves.
High crankcase temperature
(should be 150 F to 160 F
max. at seal housing).
Liquid line strainer clogged.
Clean strainer.
Excessive superheat.
Reset expansion valves.
Compression ratio too high.
Recheck design.
Discharge temperature over 275 F.
Check unit application.
Leaking suction or discharge valves.
Replace valves.