HEATING A COOLING

5F,H

Open-Drive Compressors

CONTACT ARM

RESISTANCE

CONNECT IN

SERIES WITH
CONTROL CIRCUIT

T

240
VAC

±

VAC

REFER

TO

UNIT

LABEL

WIRING DIAGRAM)

HIGH-PRESSURE

CONNECTION TO
OIL PUMP
DISCHARGE

LOW-PRESSURE
CONNECTION
TO CRANKCASE

Fig. 14 — Oil Pressure Safety Switch

SPRING DETAILS

7-LB

SPRING

R-12 USAGE

11-LB SPRING

R-22, R-502

USAGE

m

*When compressor Is received, the capacity control adjusting

stem will be backseated. (Compressor will be fully loaded under
all conditions )

Fig. 15 — Capacity Control Valve

An external adjusting stem (Fig. 15) sets the control

point (suction pressure at which first step of cylinder
unloading occurs). The control point is adjustable
as follows:

R-22 and R-502 .............................................. 0 to 85psig
R-12................................................................. 0to50psig

One full clockwise turn of adjusting stem will raise the

control point approximately 6psig with R-12, or lOpsig
with R-22 and R-502.

Control oil pressure is an indication of cylinder loading

condition (Table 6). Refer to Fig. 3-8 for location of
control oil-pressure gage connection. See Accessory

Unloader Paekage Installation Instructions for addi­

tional information.

Table 6 — Control Oil Pressures for

Cylinder Loading and Unloading

COMPRESSOR

STEP*

APPROXIMATE

CONTROL OIL PRESS. (psIg)

Loading

Unloading

5F20

1

19 8

13.0

5F30

1

2

30 0

198

20 2

130

5F40,60;

1

30.0

19.0

5H40,46,

2

26.0

160

60,66,80,

3

23 0

120

86,120,126

4

20 0

9.0

‘Capacity control reduction steps

To Adjust Control Point

1. Impose an artificial load on the compressor until

suction pressure exceeds control point.

2.

Slowly close suction valve to lower compressor

suction pressure to eontrol point pressure.

3.

When at control point pressure, turn external

adjusting stem clockwise until first step of unloading
takes place, as indicated by ehanges in control
oil pressure, current draw and sound of compressor.

Control point is now set. Reopen suction service valve.

Compressor will be fully loaded when suction pressure is
3psig (4psig with R-22 and R-502) above control point,
and will be fully unloaded when suction pressure is 4psig
(7 psig with R-22 and R-502) below control point.

5F20 AND 5F30 COMPRESSORS — Two capacity
control packages are available as accessories. One is
suitable for R-12 applications; the other for R-22 and

R-502 applications.

The adjusting stem (Fig. 15) is shipped in a backseated

(fully eounterclockwise) position. Compressor will be
fully loaded under all conditions. Adjust the capacity
control set point by the same 3-step procedure described
above for 5F40 through 5H126 compressors.