beautypg.com

3 troubleshooting – Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 37

background image

Form I-SC, P/N 207696 R11, Page 37

10.2.5 Cleaning the

Heat Exchanger

Ignition Controller

with Lockout, UTEC

1003-514, P/N

257010, for Option

AH3 Gas Control

Recycling Ignition

Controller, UTEC

1003-638A, P/N

257009, for Option

AH2 Gas Control

Service NOTE: If replacing

an earlier model of ignition

controller, order replace-

ment kit

P/N 257472 for

a unit with recycling gas

control Option AH2 or

P/N

257473 for Option AH3 gas

control with lockout. (Option

codes are listed on the unit

wiring diagram.)

If the main gas valve fails to open with a normal full size pilot flame established, check

for the following:

a) If voltage between black and brown leads on the main gas valve is 20 to 32 VAC

and there is no main gas flow with the built-in manual valve in FULL OPEN posi-

tion, the main valve is defective.

b) If there is no voltage between black and brown leads on the main gas valve, check

for disconnected or shorted flame sensor lead or flame sensor probe.

When the above conditions are normal and the main gas flow is still off, the ignition

controller is probably defective. Do not attempt to service the ignition controller; it does

not contain any replaceable components.

Outer Surfaces (circulating air side) - To clean the outer surfaces of the heat

exchanger, gain access by removing the inspection panels in the ductwork or remove

the ductwork.
Remove the baffles between the heat exchanger tubes; see

FIGURE 1, page 5.

(

NOTE: If the heater has been converted to high CFM (look for conversion label on the

unit), these baffles will have already been removed.) To remove the baffles, remove

the screws marked "A" in

FIGURE 1, and slide each baffle forward. Use a brush and/or

an air hose to remove accumulated dust and grease deposits from the heat exchanger

tubes and the baffles. Re-install the baffles by sliding them into the slot in the other

end of the heat exchanger and replacing the screws. Secure ductwork as necessary.
Inner Surfaces (combustion gas side) - The inner surfaces of the heat exchanger

can be reached for cleaning with the burner rack removed (See Paragraph 10.2.3.) An

air hose; a long (18 to 24-inch), 1/2" diameter stiff brush; a flashlight; and a mirror are

needed. Clean the inner surface of the heat exchanger from beneath using the brush

to "scrub" the tube walls to remove any accumulated dust, rust, and/or soot.
Re-assemble the furnace. Check for proper operation.

10.2.6 Venter Motor

Power venter motors are permanently lubricated. No oiling is required.

10.2.7 Limit Control

Check

With the heater on, completely block off the distribution air. The limit control should

open within a few minutes, shutting off gas supply to the main burners.

10.3 Troubleshooting

Reference: If the furnace is equipped with electronic modulation Option AG39 or AG40, consult the troubleshooting

chart,

FIGURE 31, page 31.

TROUBLE

PROBABLE CAUSE

REMEDY

Venter motor will

not start

1. No power to the furnace.

1. Turn on power, check supply fuses or circuit breaker.

2. No 24-volt power to venter relay.

2. Turn up thermostat, check control transformer output.

Check for loose or improper wire connections.

3. Venter relay defective.

3. Replace.

4. Defective motor or capacitor.

4. Replace defective part.

Pilot will not light -

- Venter operating

1. Manual valve not open.

1. Open manual valve.

2. Air in gas line.

2. Bleed gas line.

3. Dirt in pilot orifice.

3. Remove and clean with compressed air or solvent.

4. Gas pressure too high or too low.

4. Adjust supply pressure. (See Paragraph 6.2).

5. Kinked pilot tubing.

5. Replace tubing.

6. Pilot valve does not open.

6. If 24 volt is available at the valve, replace valve.

7. No spark:

7.