beautypg.com

4 gas controls, 0 controls (cont'd) – Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 28

background image

Form I-SC, P/N 207696 R11, Page 28

8.4 Gas Controls

8.4.1 Operating Valve

All furnaces are equipped with a 24-volt combination valve which includes the auto-

matic electric on-off valve controlled by the room thermostat, the pressure regulator,

the safety pilot valve, and the manual shutoff valve. The standard gas valve allows for

single-stage control from a single-stage, 24-volt thermostat.

WARNING

The operating valve is the prime safety shutoff. All gas supply lines

must be free of dirt or scale before connecting the unit to ensure

positive closure. See Hazard Levels, page 2.

8.4.2 Optional 2-Stage

Operation - Heating

Only Application

The standard combination control valve is replaced with a two-stage combination gas

control valve providing for low fire or high fire operation controlled by a two-stage

thermostat. First stage (low fire) is factory set (not field adjustable). Both high and low

stages are controlled by a Servo regulator, maintaining constant gas input under wide

variations in gas supply pressure. See instructions packed with the unit for specific gas

valve specifications, wiring, and operating instructions.

FIGURE 27 - Remote

Temperature Selector

(A) and Stage-Adder

Module (B) in Two-

Stage Makeup Air

Control Option AG15

FIGURE 26B -

Ductstat Bulb

(factory installed)

FIGURE 26A - Ductstat

Control in Option AG3

Factory

set at

70°F

8.4.3 Optional 2-Stage

Operation - Makeup

Air Application

Optional Ductstat with Electronic Remote Set-

point Module (Option AG15) - The sensing probe

is field-wired to a remote temperature selector. The

temperature selector has an operating range to

120°F. The remote modules are shipped separately

for field installation.
Follow the wiring diagram with the unit and the

manufacturer's instructions for wiring and installa-

tion.
There will be one module for selecting temperature

and one-stage adder module as illustrated in

FIG-

URE 27.

(A)

Adjustable range

0-100°F with a fixed

differential of 3°F.

Ductstat Bulb

in Option AG3

Model SC Duct Furnace

Front (Discharge) View

Two-stage makeup air units are equipped with a two-stage gas valve, but instead of

control from a two-stage room thermostat, the outlet air temperature is monitored and

controlled by a two-stage ductstat. When the discharge air temperature drops to the

setpoint, low fire is energized. If low fire cannot satisfy the ductstat setting, high fire is

energized.
Makeup air applications are usually adjusted to discharge an outlet air temperature

between 65°F and 75°F. In all applications, the allowable temperature rise of the fur-

nace in the installation dictates the limits of the ductstat temperature setting.
Depending on the option selection, the sensor is either connected by capillary tubing

to the unit-mounted ductstat (

FIGURES 26A and 26B) or electrically connected to a

remote electronic temperature selector (

FIGURE 27). See Paragraph 6.4.5 for instruc-

tions on locating the sensor in the ductwork.
Optional Ductstat with Capillary Tubing (Option AG3) -- The control illustrated in

FIGURE 26A has an adjustable range from 0° to 100°F with a fixed differential of 3°F.

Due to different CFM settings and outside air temperatures, the average downstream

outlet temperature may not match the ductstat setting exactly. After the installation is

complete, adjust the setpoint of the ductstat to achieve the desired average outlet air

temperature.

(B)

8.0 Controls

(cont'd)

CAUTION: Be sure

heat/cool selector

switch is set at

"Heat" position.