beautypg.com

0 electrical supply and connections (cont'd), 3 typical wiring diagrams (cont'd), Figure 25 - model sc with two-stage gas control – Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 26

background image

Form I-SC, P/N 207696 R11, Page 26

FIGURE 25 - Model SC with Two-Stage Gas Control

7

8

9

10

11

12

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

& CAPACITOR

VENTER MOTOR

B

C

W

8

12

1

2

4

11

R

Y

W

BK

W

BK

BK

BK

7

7

7

BK

BR

24

H

TD

H

BR

BR

W

23

H

TD

H

BR

7

BK

BL

W

TIME DELAY
RELAY COIL
12 - 28

22

FAN
TD HEATER

CR

22

7

BLOWER RELAY COIL

CUSTOMER'S 24V.

8 VA. MAXIMUM

FACTORY WIRING

FIELD WIRING

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

TOTAL WIRE MINIMUM RECOMMENDED

LENGTH WIRE SIZE

150 FEET #18 GA.

250 FEET #16 GA.

350 FEET #14 GA.

FIELD CONTROL WIRING

BK

13

R

R

LOW STAGE

PILOT

HIGH STAGE

BK

Y

BR

7

R

C

OPTIONAL

TWO

ST

A

GE THERMOST

AT

W1

DISCONNECT SWITCH

LINE/1/60

GRD

G

40 VA. CONTROL

TRANSFORMER

BK

Y

BL

BR

R

B

W

LIMIT

CONTROL

SWITCH

PRESSURE

COMBUSTION

NC

NO

COM

LINE VOLT

24V

10

Y

BL

R

OPTIONAL FACTORY

WIRING

8

BL

WD 126687 REV. #8

1, 2, 4, 7, 8, 10, 11,

12, 13, B, C & W

TERMINAL BLOCK --

HEATER

COMPARTMENT

SC: AH2/AH3-AG2-CL22

OPERATING SEQUENCE
- SET THERMOSTAT SWITCH AT "OFF" POSITION.

- TURN ON POWER, MAIN AND PILOT MANUAL GAS VALVES.

- SET THERMOSTAT SWITCH AT "AUTO" POSITION.

- ON A CALL FOR HEAT BY THE LOW STAGE OF THERMOSTAT

- THE VENTER MOTOR IS ENERGIZED AFTER A 15 SECOND (APPROX.) TIME DELAY.

- VENTER FLOW SWITCH SWITCHES FROM N.C. TO N.O. CONTACTS ENERGIZING

THE PILOT GAS VALVE AND SPARK GAP TO PRODUCE A PILOT FLAME ON EACH

OPERATING CYCLE. THE SENSING PROBE PROVES THE PRESENCE OF THE PILOT

FLAME AND ENERGIZES THE SAFETY PORTION OF THE CONTROL. THE SWITCH

ACTION DE-ENERGIZES THE SPARK GAP AND ENERGIZES THE MAIN VALVE.

THE MAIN GAS IGNITES AND UNIT FIRES AT LOW RATE.

- ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT, THE UNIT FIRES AT FULL RATE.

- SET THERMOSTAT SWITCH AT "OFF" POSITION FOR SHUTDOWN.

ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

- USE #14 GA. WIRE FOR LINE WIRING ON UNIT.

TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZE SHOULD BE OF A SIZE

- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED

- THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS:

- THE FOLLOWING CONTROLS ARE FACTORY INSTALLED OPTIONS:

FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

THERMOSTAT

- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

BY OTHERS: STARTER COIL

FAN CONTROL

NOTES

- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

A TEMPERATURE RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR SENSOR

LEAD WIRE WHICH MUST BE 150 DEGREES C.

- BLOWER MOTOR IS ENERGIZED FROM FAN TIME DELAY.

(SEE NOTES)

PIL

O

T

AL

TERNA

TE

W

.R.

T

WO

ST

A

GE

REDUNDANT

GAS V

AL

VE

R

BL

3

HIGH

STG

4

BK

STG

2

LO

W

1

BR

HIGH

STG

HI

PV

PIL

O

T

STG

LO

W

C

MV

REDUNDANT

GAS V

AL

VE

HONE

Y

WELL T

WO

ST

A

GE

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25

TIMES THE MAXIMUM TOTAL INPUT AMPS.

- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.

CONTACTS

FAN TD

1

3

- BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.

W2

BK

7

BL

BK

IGNITION

CONTROLLER

PROBE

GRND

SPARK

FLAME SENSING

MV/PV

MV

SENSE

TH

PV

G

BURNER

GND

BR

Y

R

24V GND

GND BURNER

- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,

THE SAFETY SWITCH CLOSES THE MAIN VALVE AND RECYCLES THE

SPARK GAP.

ON UNITS EQUIPPED WITH LOCKOUT CONTROL, IF PILOT IS NOT

ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR ONE

HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER TO
THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)

M3(1)

M4(3)

VENTER TIME DELAY

RELAY CONTACTS

M1(4)

M2(5)

RELAY CONTACTS

VENTER TIME DELAY

7.0 Electrical Supply and Connections (cont'd)

7.3 Typical Wiring Diagrams (cont'd)