beautypg.com

Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 15

background image

Form I-SC, P/N 207696 R11, Page 15

2. Install the Vent Pipe and Combustion Air Pipe Runs - Use the type of pipe speci-

fied in Requirement No. 1, pages 9-10. Comply with requirements in Requirement No.

2, page 10, when attaching pipes to the heater.
Seal all joints. Due to the high temperature,

do not enclose the exhaust pipe or place

pipe closer than 6" (152 mm) to combustible material. Extend the runs close to the

wall location selected in Step 1. Support pipes as required in Requirement No. 5, page

12.
3. Prepare a hole through the outside wall for the 8" (203mm) diameter combus-

tion air pipe. Outside wall construction thickness should be between 1" (25mm) mini-

mum and 48" (1143mm) maximum. The larger diameter combustion air pipe serves

as clearance for the vent pipe on non-combustible construction. A thimble may be

required depending on wall construction and/or local codes.
4. Prepare the Concentric Adapter Box

a) Attach the brackets to the box. Follow the instructions in FIGURE 11.

WARNING

All vent terminals must be positioned or located away from fresh air intakes, doors and windows

to preclude combustion products from entering occupied space. Failure to comply could result in

severe personal injury or death and/or property damage.

FIGURE 11 - Brackets

for Attaching the

Concentric Adapter Box

to the Wall

1) Attach the Brackets to the Box - The 6”

(152mm) portion of each bracket is

designed with five 7/32” diameter holes

so that attachment to the box can be

adjusted.

If the wall is combustible, position brackets to

allow for a 2” (51mm) clearance between the

box and thewall.

Adjust bracket attachment to allow for the slight

downward pitch of the terminal vent pipe.

After careful positioning, use sheetmetal screws

to attach the brackets. NOTE: If any holes are

made in the box in error, they must be sealed.

2) Attach the Box to the Wall (Step 5)

When the box is attached to the wall in Step 5,

use the 2-1/2” (64mm) portion of the brackets.

To adjust to construction each bracket has

three 7/32” diameter holes.

b) Attach the outside portion of the combustion air pipe to the box. Determine

the length by measuring the bracket length from box to wall, plus the wall thickness,

plus 2" (51 mm). (The inlet air pipe should extend beyond the outside wall

approximately 2" (51mm).)
Attach the inlet air pipe to the collar of the concentric adapter with sheetmetal screws

and seal.
5. Attach the concentric adapter box to the wall. Insert the combustion air pipe

through the wall.

Attach the brackets (FIGURE 11) to the wall. On the outside, caulk or

flash the inlet air pipe. Flashing is field-supplied.
6. Position the inlet guard over the end of the combustion air pipe. See FIGURE 12,

page 16. Attach the guard to the inlet air pipe with the four 1/2" long screws provided.
7. Determine length and install the double-wall terminal vent pipe.

a) Determine length of pipe. The length of the vent pipe is determined by the instal-

lation within the maximum and minimum requirements. See

FIGURE 12, to determine

lengths of each segment and calculate the total length required. The vent pipe extend-

ing through the box and the inlet air pipe

must be one piece of double-wall vent pipe

without joints. The transition to the single-wall or Category III vent pipe run, must be

a maximum of 6” (152mm) from the heater side of the box.
b) Install double-wall terminal vent pipe. Being sure the vent pipe is in the proper

flow direction, slide the end through the box. Position the vent pipe so that it will extend