beautypg.com

Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 19

background image

Form I-SC, P/N 207696 R11, Page 19

FIGURE 15 - Assemble Concentric Adapter Box, Outdoor Combustion Air Pipe, and Double-Wall

Vent Pipe

Concentric

Adapter Box

Mounting Brackets

X = length of

combustion air pipe required

through and above the roof.

Height from box to top of inlet air

pipe must not exceed 48” (1219mm).

Minimum height above the roof is

18” (457mm) and must be higher

than anticipated snow depth.

First, attach Combustion Air Pipe and install the

Concentric Box
1)
Determine length (X) of pipe (see requirements
on the left).
2) Attach the pipe to the collar on the box.
3) Attach the brackets to the roof.

V

ent Flow

22” (559mm) minimum

Cold Climate NOTE:

In geographic areas

where the design ambient

is -10°For lower, this

minimum height

is 34” (864mm).

Collar for Indoor Portion of

the Combustion Air Pipe

Double-Wall Vent Pipe -

Extend length of double-wall

vent pipe a maximum of 6”

(152mm) below the box.

After box is installed, install Concentric Vent Pipe -

One piece of continuous double-wall pipe must extend

from a minimum of 3” (76mm) above the outer com-

bustion air pipe to a maximum of 6” (152mm) below
the box.
(NOTE: Vent pipe does not attach to the box;
it must be supported
.)
1) Calculate height (see requirements on the left).
2) Be sure vent flow marking on pipe is in the right
direction.
3) Slide pipe through the box and the outer inlet air pipe.
4) Attach to vent run no more than 6” (152mm) from the
adapter box. See instructions on page 12.

Vent pipe

extending

through the

box and the

combustion

air pipe MUST

be one continuous

piece of double-

wall vent pipe.

A second section

of double-wall pipe

is permitted, joining

the long continuous

piece of vent pipe a

minimum of 3” (76mm)

above the top of the

combustion air pipe.

3” (76mm)

minimum

FIGURE 17 - Install Combustion Air Inlet and Vent Terminal

FIGURE 16 - Slide attached

Combustion Air Pipe up

through the Roof

Outside View with

concentric adapter

box attached to under-

side of roof.

Install field-supplied
flashing at roof opening.

Snow Clearance

18” (457mm)

minimum

(NOTE: Maximum

from concentric

adapter box is

48” (1219mm)

9. Attach the indoor combustion air pipe. Use sheetmetal screws to attach the sin-

gle-wall combustion air pipe run to the collar on the concentric adapter box. Seal with

tape or sealant. If using 7” pipe on Sizes 200-400, install a taper type enlarger as illus-

trated in

FIGURE 9B, page 13.

SECOND, Install the Exhaust (Vent) Terminal.

Follow the instructions in FIGURE 2, page 3.

FIRST, Install Combustion Air Inlet.

1) Slide the combustion air inlet over the vent pipe.

2) Fasten bottom of inlet to the combustion air pipe

with sheetmetal screws. Be sure not to penetrate

the vent pipe.

3) At the top, completely seal the space between the

vent pipe and the air inlet with silicone.

Double-wall V

ent Pipe

Cold Climate NOTE: In geographic

areas where the design ambient is

-10°F or lower, this minimum height

is 24” (610 mm)

Single-wall Combustion Air Pipe