beautypg.com

0 electrical supply and connections, 1 general, 2 supply voltage and wiring – Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 24: 0 mechanical (cont'd), 4 duct furnace airflow (cont'd)

background image

Form I-SC, P/N 207696 R11, Page 24

7.0 Electrical

Supply and

Connections

7.1 General

FIGURE 23A -

Discharge Air Sensor

Holder, P/N 115850,

used in Makeup Air

Option AG15

Secure sensor in clip.

Position holder so that it

shields sensor from direct

airflow.

FIGURE 23B - A

Discharge Air Sensor

and Mixing Tube are

used in Electronic

Modulation Options

AG8, AG9, and AG39

6.0 Mechanical

(cont'd)

6.4 Duct Furnace

Airflow (cont'd)

as equal to the square root of 4AB/3.14. "A" and "B" are the duct cross-sectional

dimensions.

Example:

Supply ductwork cross-sectional dimension is

24" x 12" (610mm x 305mm).

5 x

4 x 12 x 24

3.14

= 96"

5 x

4 x 305 x 610

3.14

= 2435mm

Solution: Locate the sensor a minimum of 96" (2435mm)

from the outlet of the unit.

NOTE: If the length of the discharge duct is less than 8 ft (2.4M), a mixing vane is

recommended for mixing the discharge air.

Do not mount the sensor in the ductwork after a split in the supply as that will

cause loss of control in the duct that does not house the sensor.

3. The position of the sensor holder or mixing tube is important. The holder in

FIGURE 23A will extend 9-3/16” (233mm) into the ductwork. The mixing tube in

FIGURE 23B is 12" (305mm) long.

In horizontal ductwork, locate the sensor assembly in the top, middle of the duct

with the sensor probe extending vertically down into the center of the airstream.

In vertical ductwork, locate the sensor assembly in the middle of the side of the

duct that corresponds with the top middle of the discharge outlet.
Turn the holder so that the element will be shielded from direct airflow and will

sense the air temperature as it flows through the holes in the holder.
At the selected location in the ductwork, mark the diamond-shaped hole

[approximately 1” x 1” (25mm x 25mm)] required for the sensor holder or the round

hole needed for the mixing tube. Cut the hole no larger than required.

4. Option AG15 - Push the element into the clip in the holder. Determine where the

sensor wire should enter the box and remove the knockout. Slide the holder into

the ductwork. Using four field-supplied No. 6 sheetmetal screws, attach the box

portion of the holder to the ductwork. Attach a field-supplied cable connector to the

box, connect the sensor wire, and attach the box cover.

Options AG8, AG9, and AG39 - Slide the mixing tube into the ductwork and

attach the sensor. Connect the wires as shown on the wiring diagram.

Option AG40 - Follow the instructions provided with the field-supplied sensor.

Refer to the wiring diagram with the unit and the field-supplied sensor to connect

the wires.

6.4.5 Discharge Air Sensor for Makeup Air Application (cont'd)

Instructions for Installing Discharge Air Sensor in the Ductwork (cont'd)

WARNING

If you turn off the

power supply, turn off

the gas. See Hazard

Levels, page 2.

All electrical wiring and connections including electrical grounding must be made in

accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in

Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C22.l. Check any local

ordinances or gas company requirements that apply.

7.2 Supply Voltage and Wiring

Check the rating plate on the heater for the supply voltage and the current require-

ments. A separate line voltage supply with fused disconnect switch should be run

directly from the main electrical panel to the unit, making connections in the junction

box. Refer to

FIGURE 2, Paragraph 4.2. Seal all electrical entrance openings with

field-supplied bushings.

A disconnect switch is available as optional equipment or may be supplied locally.

When installing the disconnect switch, be careful that the conduit and switch housing

are clear of all service panels. Allow at least four feet (1.2M) of service room between

the disconnect switch and any removable service panels. When providing or replacing

fuses in a fusible disconnect switch, use dual element time delay fuses and size 1.25

times the maximum total input amps.
See typical wiring diagram in

FIGURE 24 or 25; a specific wiring diagram can be found

in the heater junction box. See separate instruction sheets for any optional equipment

provided. Electrical options are identified on the wiring diagram on the heater.