Linkage, I/o points – Carrier RTU OPEN 11-808-427-01 User Manual
Page 79
![background image](/manuals/69183/79/background.png)
RTU Open
73
Linkage
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Linkage
Properties
>
Equipment
>
Linkage
Point Name/Description
Range
Linkage Collector – Allows access to the Collector's details.
Airside Linkage Status
– If Active, the controller is part of a linked system. If Not
Active
, the controller is a stand-alone device.
R:
Active/Not Active
If Airside Linkage Status is Active, the following provide information received from
the VVT Master (as applicable):
Occupancy Status
Space Temperature
Occupied Cooling Setpoint
Occupied Heating Setpoint
Unoccupied Cooling Setpoint
Unoccupied Heating Setpoint
Indoor Air CO2
Space Relative Humidity
I/O Points
The values shown on the I/O Points Properties page are the raw values at the I/O objects and may not match
values shown on status displays that are affected by control program logic.
i-Vu users logged in as Power User and above are able to edit various parameters associated with the input
channels and the display names for all channels.
We strongly recommend that you leave these parameters at their defaults. The RTU Open is not a
programmable controller. I/O can only be used for the purpose designed in the equipment control program.
Modifying these parameters may result in unpredictable equipment control.
See Wiring inputs and outputs (page 12) for more information. This table lists each of the I/O Channels, their
functions, associated hardware, and terminal numbers.
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
I/O Points
N/A
Point Name/Description
Space Temp
– The value of the Optional SPT (Rnet) sensor. Also allows i-Vu and Field Assistant users access to
sensor configuration. See Carrier Sensors Installation Guide for additional details.
input 1
– Input Channel 1; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space RH.
input 2
– Input Channel 2; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space Relative Humidity.
input 6
– Input Channel 6; 10K Thermistor only. Supply Air Temperature.
input 7
– Input Channel 7; 10K Thermistor only. Outside Air Temperature.
input 10
– Input Channel 10; 10K Thermistor only. Space Temperature (T55, 56, 59).