Linkage, I/o points – Carrier RTU OPEN 11-808-427-01 User Manual

Page 79

background image

RTU Open

73

Linkage

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Linkage

Properties

>

Equipment

>

Linkage

Point Name/Description

Range

Linkage Collector – Allows access to the Collector's details.

Airside Linkage Status

– If Active, the controller is part of a linked system. If Not

Active

, the controller is a stand-alone device.

R:

Active/Not Active

If Airside Linkage Status is Active, the following provide information received from

the VVT Master (as applicable):
Occupancy Status

Space Temperature

Occupied Cooling Setpoint

Occupied Heating Setpoint

Unoccupied Cooling Setpoint

Unoccupied Heating Setpoint

Indoor Air CO2

Space Relative Humidity

I/O Points

The values shown on the I/O Points Properties page are the raw values at the I/O objects and may not match

values shown on status displays that are affected by control program logic.
i-Vu users logged in as Power User and above are able to edit various parameters associated with the input

channels and the display names for all channels.
We strongly recommend that you leave these parameters at their defaults. The RTU Open is not a

programmable controller. I/O can only be used for the purpose designed in the equipment control program.

Modifying these parameters may result in unpredictable equipment control.
See Wiring inputs and outputs (page 12) for more information. This table lists each of the I/O Channels, their

functions, associated hardware, and terminal numbers.

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

I/O Points

N/A

Point Name/Description

Space Temp

– The value of the Optional SPT (Rnet) sensor. Also allows i-Vu and Field Assistant users access to

sensor configuration. See Carrier Sensors Installation Guide for additional details.
input 1

– Input Channel 1; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space RH.

input 2

– Input Channel 2; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space Relative Humidity.

input 6

– Input Channel 6; 10K Thermistor only. Supply Air Temperature.

input 7

– Input Channel 7; 10K Thermistor only. Outside Air Temperature.

input 10

– Input Channel 10; 10K Thermistor only. Space Temperature (T55, 56, 59).