Start-up

38

RTU Open

Use Power Exhaust Test to activate and deactivate the power exhaust (BO - 8) output.

Use Economizer Test to set the (AO - 1) economizer output to any value from 0 to 100% of configured

output (2-10 Vdc or 4-20 mA).

Analog Output 2 Test

(AO - 2) is currently unused and does not require testing.

Service Test mode does not timeout. Return all test variables to Disable or 0.00. Set Service Test to

Disable

or cycle power to the RTU Open to return to normal operation.


Configuring the RTU Open's properties

To start up the RTU Open, you must configure certain points and properties. Appendix C is a complete list of

all the points and properties, with descriptions, defaults, and ranges. These properties affect the unit

operation and/or control. Review and understand the meaning and purpose of each property before changing

it.

Unit Configuration properties (page 38)

Setpoint Configuration properties (page 40)

Service Configuration properties (page 41)

See Appendix A (page 59) for a complete list of the controller's points/properties.

Unit Configuration properties

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Configuration

>

Unit Configuration

HOME

>

CONFIG

>

UNIT

Point Name/Description

Default/Range

Fan Mode

– The supply fan's operating mode.

Options:

Auto

- The fan cycles on/off in conjunction with heating or cooling.

Continuous

- The fan runs continuously during occupancy & intermittently during

unoccupied periods with heating or cooling.

Always On

- The fan runs continuously regardless of occupancy or calls for heating and

cooling.

D:
R:

Continuous
Auto

Continuous

Always On

Occupancy Source

- The method that the controller uses to determine occupancy.

Options:

Always Occupied

= Controller operates continuously as occupied.

BACnet Schedule

= Controller follows a schedule set up in the i-Vu application or Field

Assistant.

BAS On/Off

= Occupancy is set over the network by another device or a third party BAS.

Remote Occ Input

= Occupancy is set by a remote contact.

D:
R:

Always Occupied
Always Occupied

BACnet Schedule

BAS On/Off

Remote Occ Input

Input 1 Function

– The type of sensor (4-20 mA) connected to terminals J4 – 4, 5, & 6.

D:
R:

No Sensor
No Sensor

IAQ Sensor

OAQ Sensor

Space RH Sensor