Configuring the rtu open's properties, Unit configuration properties – Carrier RTU OPEN 11-808-427-01 User Manual
Page 44
Start-up
38
RTU Open
•
Use Power Exhaust Test to activate and deactivate the power exhaust (BO - 8) output.
•
Use Economizer Test to set the (AO - 1) economizer output to any value from 0 to 100% of configured
output (2-10 Vdc or 4-20 mA).
•
Analog Output 2 Test
(AO - 2) is currently unused and does not require testing.
•
Service Test mode does not timeout. Return all test variables to Disable or 0.00. Set Service Test to
Disable
or cycle power to the RTU Open to return to normal operation.
Configuring the RTU Open's properties
To start up the RTU Open, you must configure certain points and properties. Appendix C is a complete list of
all the points and properties, with descriptions, defaults, and ranges. These properties affect the unit
operation and/or control. Review and understand the meaning and purpose of each property before changing
it.
•
Unit Configuration properties (page 38)
•
Setpoint Configuration properties (page 40)
•
Service Configuration properties (page 41)
See Appendix A (page 59) for a complete list of the controller's points/properties.
Unit Configuration properties
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Configuration
>
Unit Configuration
HOME
>
CONFIG
>
UNIT
Point Name/Description
Default/Range
Fan Mode
– The supply fan's operating mode.
Options:
Auto
- The fan cycles on/off in conjunction with heating or cooling.
Continuous
- The fan runs continuously during occupancy & intermittently during
unoccupied periods with heating or cooling.
Always On
- The fan runs continuously regardless of occupancy or calls for heating and
cooling.
D:
R:
Continuous
Auto
Continuous
Always On
Occupancy Source
- The method that the controller uses to determine occupancy.
Options:
Always Occupied
= Controller operates continuously as occupied.
BACnet Schedule
= Controller follows a schedule set up in the i-Vu application or Field
Assistant.
BAS On/Off
= Occupancy is set over the network by another device or a third party BAS.
Remote Occ Input
= Occupancy is set by a remote contact.
D:
R:
Always Occupied
Always Occupied
BACnet Schedule
BAS On/Off
Remote Occ Input
Input 1 Function
– The type of sensor (4-20 mA) connected to terminals J4 – 4, 5, & 6.
D:
R:
No Sensor
No Sensor
IAQ Sensor
OAQ Sensor
Space RH Sensor