beautypg.com

Inputs, Binary outputs, Analog output – Carrier RTU OPEN 11-808-427-01 User Manual

Page 20: To wire inputs and outputs

background image

Installation

14

RTU Open

Inputs

These RTU Open inputs accept the following signal types:

These

inputs...

Support this

signal type...

Description

1, 2

4-20 mA

The input resistance on the positive (+) terminal is 250 Ohms.

The Aux Power Out terminal is capable of supplying 24 Vdc to

a 4-20 mA transducer, but the total current demanded must

not exceed 40 mA. If the voltage measured from the Aux

Power Out terminal to Gnd is less than 18 Vdc, you need to

use an external power supply.

3, 5, 8, 9

Binary (24 Vac)

24 Vac voltage, resulting in a 25 mA maximum sense current

when the contacts are closed

6, 7, 10

Thermistor

10 kOhm at 77° F

11

100k Potentiometer

Typically used for 33CZT56SPT Setpoint Offset Potentiometer


Binary outputs

The RTU Open has 8 binary outputs. You can connect each output to a maximum of 24 Vac/Vdc. Each output

is a dry contact rated at 3 A, 24 V maximum, and is normally open.
To size output wiring, consider the following:

Total loop distance from the power supply to the controller, and then to the controlled device
NOTE

Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.

Acceptable voltage drop in the wire from the controller to the controlled device

Resistance (Ohms) of the chosen wire gauge

Maximum current (Amps) the controlled device requires to operate


Analog output

The RTU Open has 1 analog output that supports voltage or current devices. The controlled device must share

the same ground as the controller and have input impedance of 500 Ohms maximum for the 4-20 mA mode

on AO - 1.

To wire inputs and outputs

1

Turn

off

the RTU Open's power.

2

Connect the input wiring to the screw terminals on the RTU Open.

3

Turn

on

the RTU Open's power.