Appendix A: RTU Open Points/Properties
62
RTU Open
Point Name/Description
Default/Range
Input 5
Switch Configuration – The normal (de-energized) state for the set of contacts
terminated at Input
D:
R:
NC
NO/NC (normally
open/normally closed)
Input 8 Function
– The usage of Input 8. You must also set Input 8 Switch Configuration.
Options:
No Function
– The input is not used.
Enthalpy Switch
– Indicates enthalpy status (high or low).
Fan Status
– Proves supply fan operation.
Filter Status
– Indicates a dirty filter.
Remote Occupancy
– Sets occupancy using a hardware contact.
Door Contact
– Sets occupancy using a hardware contact.
D:
R:
Enthalpy Switch
No Function
Enthalpy Switch
Fan Status
Filter Status
Remote Occupancy
Door Contact
Input 8
Switch Configuration – The normal (de-energized) state for the set of contacts
terminated at Input
D:
R:
NO
NO/NC (normally
open/normally closed)
Input 9 Function
– The usage of Input 9. You must also set Input 9 Switch Configuration.
Options:
No Function
– The input is not used.
Humidistat
– Indicates high humidity condition.
Fan Status
– Proves supply fan operation.
Filter Status
– Indicates a dirty filter.
Remote Occupancy
– Sets occupancy using a hardware contact.
Door Contact
– Sets occupancy using a hardware contact.
D:
R:
Humidistat
No Function
Humidistat
Fan Status
Filter Status
Remote Occupancy
Door Contact
Input 9
Switch Configuration – The normal (de-energized) state for the set of contacts
terminated at Input
D:
R:
NO
NO/NC (normally
open/normally closed)
Space sensor type
- The type of local space temperature sensor.
D:
R:
T55
T55
T56 (Use for T59)
SPT Sensor
None
T5x Override Duration
– If using a T55, T56, or T59 sensor, this is the amount of time
that the controller runs in the occupied mode when a user presses the sensor's override
button for 1 to 10 seconds.
D:
R:
1 hr
0 to 24 hours
Sensor Calibration
Space Temp Calibration
– A calibration offset value to allow the local space temperature
sensor to be adjusted to match a calibrated standard measuring the temperature in the
same location.
D:
R:
0°F
-9.9 to 10°F
Supply Air Temp Calibration
– A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0°F
-9.9 to 10°F
Outside Air Temp Calibration
– A calibration offset value to allow the outside air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0°F
-9.9 to 10°F