RTU Open

45

The cooling relays are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They

calculate the desired number of stages needed to satisfy the space by comparing the Space Temperature to

the:

Effective Occupied Cooling Setpoint

when occupied

Effective Unoccupied Cooling Setpoint

when unoccupied


When the cooling algorithm preconditions have been met, the compressors are energized in stages, as

applicable. Anti-recycle timers are employed to protect the equipment from short-cycling. There are fixed

three-minute minimum on-times, and five-minute off-times for each compressor output.
During compressor operation, the RTU Open may reduce the number of active stages if the rooftop supply air

temperature falls below the Minimum Cooling SAT Setpoint. A compressor staged off in this fashion may be

started again after the normal time-guard period has expired, if the Supply Air Temperature has increased

above the Minimum Cooling SAT Setpoint.
Compressor 2 Service Alarm Timer

functions are available (one for each stage of compression). This function

tracks the number of compressor run hours and generates an alarm when the accumulated runtime exceeds

the threshold set by the adjustable compressor service alarm timers.

Economizer

The RTU Open provides an analog economizer output for rooftop units with economizer dampers. Economizer

dampers may be used to provide indoor air quality control and free cooling when outside air conditions are

suitable.
The following conditions must be true for economizer operation:

The Outdoor Air Temperature is less than the Space Temperature and less than the Economizer High

OAT Lockout Temp

setpoint

The indoor fan has been on for at least 30 seconds

The unit has a valid Supply Air Temperature input

The unit has a valid Space Temperature input

If any of the preceding conditions are not true, the economizer will be set to the Vent Dmpr Pos / DCV Min

Pos

setpoint.

If all preceding conditions are true, the economizer PID loop will modulate the damper from the Vent Dmpr

Pos / DCV Min Pos

setpoint.

The economizer moves to the Vent Dmpr Pos / DCV Min Pos setpoint if the SAT falls below the Minimum

Cooling SAT

(+ 5°F).