RTU Open

57

If Run LED shows...

And Error LED shows...

Status is..

7 flashes per second

7 flashes per second,

alternating with Run LED

Ten second recovery period after

brownout

14 flashes per second

14 flashes per second,

alternating with Run LED

Brownout

On

On

Failure. Try the following solutions:

Turn the RTU Open off, then

on.

Format the RTU Open.*

Download memory to the RTU

Open.

Replace the RTU Open.

*Formatting the controller may result in lost information and should only be done under the guidance of

Carrier Control Systems Support.



Replacing the RTU Open's battery

The RTU Open's 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of data retention

during power outages.
CAUTION

Power must be ON to the RTU Open when replacing the battery, or your date, time, and trend data

will be lost.

1

Remove the battery from the controller, making note of the battery's polarity.

2

Insert the new battery, matching the battery's polarity with the polarity indicated on the RTU Open.