Appendix A: RTU Open Points/Properties

60

RTU Open

Unit Configuration

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Configuration

>

Unit Configuration

HOME

>

CONFIG

>

UNIT

Point Name/Description

Default/Range

Fan Mode

– The supply fan's operating mode.

Options:

Auto

- The fan cycles on/off in conjunction with heating or cooling.

Continuous

- The fan runs continuously during occupancy & intermittently during

unoccupied periods with heating or cooling.

Always On

- The fan runs continuously regardless of occupancy or calls for heating and

cooling.

D:
R:

Continuous
Auto

Continuous

Always On

Unit Start Delay

– How long the controller delays normal operation after power is

restored. Typically used to prevent excessive demand when recovering from a power

failure.

D:
R:

5 sec
0 to 30 sec

Fan Off Delay

– How long the supply fan runs after receiving a valid stop command.

D:
R:

90 seconds
0 to 180 seconds

Minimum Cooling SAT

– In cooling mode, the cooling outputs are controlled so that the

supply air temperature does not drop below this value.

D:
R:

50°F
45 to 75°F

Maximum Heating SAT

– In heating mode, the heating outputs are controlled so the

supply air temperature does not rise above this value.

D:
R:

120°F
85 to 150°F

Vent Dmpr Pos / DCV Min Pos

– The minimum outdoor air damper position maintained

during occupied periods.

D:
R:

50% Open
0 to 100% Open

DCV Max Vent Damper Pos

– The maximum outdoor air damper position allowed while

DCV is active.

D:
R:

50% Open
10 to 60% Open

Supply Fan Service Alarm Timer

– A Supply Fan Runtime alarm is generated when the

supply fan run hours exceed this value. Set to 0 to disable.

D:
R:

600 hr
0 to 9999 hr

Compressor 1 Service Alarm Timer

– A Compressor 1 Runtime alarm is generated when

the compressor 1 run hours exceed this value. Set to 0 to disable.

D:
R:

0 hr
0 to 9999 hr

Compressor 2 Service Alarm Timer

– A Compressor 2 Runtime alarm is generated when

the compressor 2 run hours exceed this value. Set to 0 to disable.

D:
R:

0 hr
0 to 9999 hr

Filter Service Alarm Timer

– The amount of time the fan will run before generating a

Filter Alarm

. Set to 0 to disable the alarm and reset accumulated fan hours.

D:
R:

600 hr
0 to 9999 hr

Pushbutton Override

– Enables or disables the use of a pushbutton override from a local

space temperature sensor.

D:
R:

Enable
Disable/Enable

Cooling Lockout Temp

– The outdoor air temperature at which cooling is inhibited.

D:
R:

45°F
0 to 80°F

Economizer High OAT Lockout

– The outdoor air temperature at which economizer

cooling is inhibited.

D:
R:

75°F
55 to 80°F