Appendix A: RTU Open Points/Properties
68
RTU Open
Point Name/Description
Default/Range
Occupied High CO2 Alarm Limit
– The value that the CO
2
sensor must exceed to
generate an IAQ Alarm in the occupied mode. There is a fixed hysteresis of 100ppm
for return to normal. Requires a space CO2 sensor and Configuration >Unit
Configuration
>Input 1 (or 2) Function set to IAQ Sensor.
D:
R:
1200ppm
0 to 9999 ppm
Service Configuration
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Configuration
>
Service Configuration
HOME > CONFIG > SERVICE
Point Name/Description
Default/Range
Unit Type
– The type of equipment that the RTU Open is controlling.
Options:
Heat/Cool
– Standard rooftop air handling unit.
HP O/B Ctrl
– Heat Pump application, uses reversing valve output to control heating
and cooling.
HP Y1/W1 Ctrl
– Carrier Heat Pump application only.
D:
R:
Heat/Cool
Heat/Cool
HP O/B Ctrl
HP Y1/W1 Ctrl
Compressor Stages
– The number of mechanical cooling stages.
D:
R:
One Stage
One Stage
Two Stages
Economizer Exists
– Set to Yes to enable economizer control for units equipped with
an economizer damper.
D:
R:
No
No/Yes
Heat Type
– The type of heating that the unit has.
D:
R:
Electric
Electric/Gas
Number Of Heat Stages
– The number of heat stages.
D:
R:
2
1 /2 /0 (no heating)
Continuous Occupied Exhaust
– Configures the exhaust fan control strategy (BO-8). If
Yes
, the power exhaust runs continuously in occupied mode and is off in unoccupied
mode. If No, the power exhaust is controlled by the Power Exhaust Setpoint.
D:
R:
No
No/Yes
Indoor CO2 Sensor Value @min (ma)
– The CO2 value that corresponds to a 4mA
input at the appropriate input channel.
D:
R:
0 ppm
0 to 9999 ppm
Indoor CO2 Sensor Value @max (ma)
– The CO2 value that corresponds to a 20mA
input at the appropriate input channel.
D:
R:
2000 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @min (ma)
– The CO2 value that corresponds to a 4 mA
input at the appropriate input channel.
D:
R:
0 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @max (ma)
– The CO2 value that corresponds to a 20 mA
input at the appropriate input channel.
D:
R:
2000 ppm
0 to 9999 ppm