Appendix A: RTU Open Points/Properties

68

RTU Open

Point Name/Description

Default/Range

Occupied High CO2 Alarm Limit

– The value that the CO

2

sensor must exceed to

generate an IAQ Alarm in the occupied mode. There is a fixed hysteresis of 100ppm

for return to normal. Requires a space CO2 sensor and Configuration >Unit

Configuration

>Input 1 (or 2) Function set to IAQ Sensor.

D:
R:

1200ppm
0 to 9999 ppm


Service Configuration

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Configuration

>

Service Configuration

HOME > CONFIG > SERVICE

Point Name/Description

Default/Range

Unit Type

– The type of equipment that the RTU Open is controlling.

Options:

Heat/Cool

– Standard rooftop air handling unit.

HP O/B Ctrl

– Heat Pump application, uses reversing valve output to control heating

and cooling.

HP Y1/W1 Ctrl

– Carrier Heat Pump application only.

D:
R:

Heat/Cool
Heat/Cool

HP O/B Ctrl

HP Y1/W1 Ctrl

Compressor Stages

– The number of mechanical cooling stages.

D:
R:

One Stage
One Stage

Two Stages

Economizer Exists

– Set to Yes to enable economizer control for units equipped with

an economizer damper.

D:
R:

No
No/Yes

Heat Type

– The type of heating that the unit has.

D:
R:

Electric
Electric/Gas

Number Of Heat Stages

– The number of heat stages.

D:
R:

2

1 /2 /0 (no heating)

Continuous Occupied Exhaust

– Configures the exhaust fan control strategy (BO-8). If

Yes

, the power exhaust runs continuously in occupied mode and is off in unoccupied

mode. If No, the power exhaust is controlled by the Power Exhaust Setpoint.

D:
R:

No
No/Yes

Indoor CO2 Sensor Value @min (ma)

– The CO2 value that corresponds to a 4mA

input at the appropriate input channel.

D:
R:

0 ppm
0 to 9999 ppm

Indoor CO2 Sensor Value @max (ma)

– The CO2 value that corresponds to a 20mA

input at the appropriate input channel.

D:
R:

2000 ppm
0 to 9999 ppm

Outdoor CO2 Sensor Value @min (ma)

– The CO2 value that corresponds to a 4 mA

input at the appropriate input channel.

D:
R:

0 ppm
0 to 9999 ppm

Outdoor CO2 Sensor Value @max (ma)

– The CO2 value that corresponds to a 20 mA

input at the appropriate input channel.

D:
R:

2000 ppm
0 to 9999 ppm