RTU Open

67

Alarm Configuration

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Configuration

>

Alarm Configuration

HOME > CONFIG > ALARMS

Point Name/Description

Default/Range

Space Temperature Alarm

Occupied Alarm Hysteresis

– This value is added to the occupied high effective

setpoint and subtracted from the occupied low effective setpoint to establish the

occupied high and low limits that the space temperature must exceed before an

occupied SPT alarm is generated. The alarm returns to normal when the space

temperature drops below the high effective setpoint or rises above the low effective

setpoint.

D:
R:

3°F
0 to 20°F

Alarm Delay (min/deg)

– Determines the amount of delay before an occupied space

temperature alarm is generated when the controller transitions to the occupied mode.

The delay time equals this value multiplied by the difference between the sensor

temperature and occupied alarm setpoint plus 15 minutes.

D:
R:

10 minutes
0 to 60 minutes

Unoccupied Low SPT Alarm Limit

–The value that the space temperature must drop

below to generate a Space Temperature Alarm in the unoccupied mode. There is a

fixed hysteresis of 1° F for return to normal.

D:
R:

45°F
-60 to 250°F

Unoccupied High SPT Alarm Limit

– The value that the space temperature must

exceed to generate a Space Temperature Alarm in the unoccupied mode. There is a

fixed hysteresis of 1° F for return to normal.

D:
R:

90°F
-60 to 250°F

Supply Air Temperature Alarm

Low SAT Alarm Limit

– The value that the supply air temperature must drop below to

generate a Supply Air Temp Alarm. There is a fixed hysteresis of 1° F for return to

normal.

D:
R:

45°F
-60 to 250°F

High SAT Alarm Limit

– The value that the supply air temperature must exceed to

generate a Supply Air Temp Alarm. There is a fixed hysteresis of 1° F for return to

normal.

D:
R:

120°F
-60 to 250°F

Space Humidity Alarm

Low Space Humidity Alarm Limit

– The value that the relative humidity must drop

below to generate a Low Space Humidity Alarm. Requires a space relative humidity

transmitter and Configuration >Unit Configuration >Input 1 (or 2) Function set to

Space RH Sensor

.

D:
R:

30%
0 – 99 %

High Space Humidity Alarm Limit

– The value that the relative humidity must rise

above to generate a High Space Humidity Alarm. Requires a space relative humidity

transmitter and Configuration >Unit Configuration >Input 1 (or 2) Function set to

Space RH Sensor

.

D:
R:

70%
0 – 99 %

IAQ/Ventilation Alarm