Setpoint properties, E 40) – Carrier RTU OPEN 11-808-427-01 User Manual
Page 46
![background image](/manuals/69183/46/background.png)
Start-up
40
RTU Open
Point Name/Description
Default/Range
Input 9
Switch Configuration – The normal (de-energized) state for the set of contacts
terminated at Input
D:
R:
NO
NO/NC (normally
open/normally closed)
Space sensor type
- The type of local space temperature sensor.
D:
R:
T55
T55
T56 (Use for T59)
SPT Sensor
None
Setpoint properties
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Configuration
>
Setpoints
HOME > CONFIG > SETPOINT
Select a color band on the setpoint graph to see the current setpoints in the Heating and Cooling fields. See setpoint
descriptions below.
Point Name/Description
Default/Range
Occupied Heating
– Green
The heating setpoint the controller maintains while in occupied mode.
D:
R:
70°F
-40 to 245°F
Occupied Cooling
– Green
The cooling setpoint the controller maintains while in occupied mode.
D:
R:
74°F
-40 to 245°F
Unoccupied Heating
– Gray
The heating setpoint the controller maintains while in unoccupied mode.
D:
R:
55°F
45 to 100°F
Unoccupied Cooling
– Gray
The cooling setpoint the controller maintains while in unoccupied mode.
D:
R:
90°F
-40 to 245°F