Setpoint properties, E 40) – Carrier RTU OPEN 11-808-427-01 User Manual

Page 46

background image

Start-up

40

RTU Open

Point Name/Description

Default/Range

Input 9

Switch Configuration – The normal (de-energized) state for the set of contacts

terminated at Input

D:
R:

NO
NO/NC (normally

open/normally closed)

Space sensor type

- The type of local space temperature sensor.

D:
R:

T55
T55

T56 (Use for T59)

SPT Sensor

None



Setpoint properties

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Configuration

>

Setpoints

HOME > CONFIG > SETPOINT

Select a color band on the setpoint graph to see the current setpoints in the Heating and Cooling fields. See setpoint

descriptions below.

Point Name/Description

Default/Range

Occupied Heating

– Green

The heating setpoint the controller maintains while in occupied mode.

D:
R:

70°F
-40 to 245°F

Occupied Cooling

– Green

The cooling setpoint the controller maintains while in occupied mode.

D:
R:

74°F
-40 to 245°F

Unoccupied Heating

– Gray

The heating setpoint the controller maintains while in unoccupied mode.

D:
R:

55°F
45 to 100°F

Unoccupied Cooling

– Gray

The cooling setpoint the controller maintains while in unoccupied mode.

D:
R:

90°F
-40 to 245°F