Wiring specifications

Cable from sensor to controller:

If <100 ft (30.5 meters) 22 AWG, unshielded

If >100 ft (30.5 meters) 22 AWG, shielded

Maximum length:

500 feet (152 meters)

To wire an enthalpy switch (outdoor air) to the controller

An enthalpy switch is typically mounted in the outdoor air inlet.

Wiring diagram for a field-installed enthalpy switch:


NOTES

Factory-installed enthalpy switches terminate at J2 wires 6 (switch input) and 7 (24 Vac).

Input channel must be configured for the enthalpy contact (N.O. or N.C.) that you use.