beautypg.com

Linkage – Carrier RTU OPEN 11-808-427-01 User Manual

Page 59

background image

RTU Open

53

High Space Relative Humidity

- The RTU Open generates this alarm when the space humidity exceeds the

Alarm Configuration

> High Space Humidity Alarm Limit setpoint for 10 minutes. This alarm is inhibited until

the RTU runs for 15 minutes to allow for system stabilization after startup.
Low Space Relative Humidity

- The RTU Open generates this alarm when the space humidity falls below the

Alarm Configuration

> Low Space Humidity Alarm Limit setpoint for 5 minutes. This alarm is inhibited until

the RTU runs for 5 minutes to allow for system stabilization after startup.
High CO2

- The RTU Open generates this alarm when the space CO2 level exceeds the Alarm Configuration >

Occupied High CO2 Alarm Limit

setpoint for 1-minute. This alarm will be inhibited until the RTU has been

running for 2-minutes to allow for system stabilization after startup.
Supply Fan Runtime

- The RTU Open generates a this alarm when the accumulated runtime exceeds the Unit

Configuration

> Supply Fan Service Alarm Timer value (when not set to 0). This alarm is most commonly

used to indicate an equipment maintenance interval is due. The supply fan runtime accumulator may be reset

by setting the Maintenance > Reset Supply Fan Runtime Alarm to Clear, and then back to Run –

acknowledging each selection by clicking the OK button when it appears. Setting Unit Configuration > Supply

Fan Service Timer

value to 0 disables the supply fan runtime alarm function.

Compressor 1 Runtime

- The RTU Open generates this alarm when the accumulated runtime exceeds the

Unit Configuration

> Compressor 1 Service Alarm Timer value (when not set to 0). This alarm is most

commonly used to indicate an equipment maintenance interval is due. The Compressor 1 Runtime

accumulator may be reset by setting the Maintenance > Reset Comp 1 Runtime Alarm to Clear, and then

back to Run – acknowledging each selection by clicking the OK button when it appears. Setting Unit

Configuration

> Compressor 1 Service Timer value to 0 disables the Compressor 1 Runtime alarm function.

Compressor 2 Runtime

- The RTU Open generates this alarm when the accumulated runtime exceeds the

Unit Configuration

> Compressor 2 Service Alarm Timer value (when not set to 0). This alarm is most

commonly used to indicate an equipment maintenance interval is due. The Compressor 2 runtime

accumulator may be reset by setting the Maintenance > Reset Comp 2 Runtime Alarm to Clear, and then

back to Run – acknowledging each selection by clicking the OK button when it appears. Setting Unit

Configuration

> Compressor 2 Service Timer value to 0 disables the Compressor 2 runtime alarm function.

Note that this function is unavailable if the Service Configuration > Compressor States value is not set to Two

Stages

.

Filter

- The RTU Open generates this alarm when the accumulated runtime exceeds the Unit Configuration >

Filter Service Alarm Timer

value (when not set to 0). This alarm is most commonly used to indicate a filter

replacement is due. Reset the filter service runtime accumulator by setting the Maintenance > Reset Filter

Runtime Alarm

to On, back to Off, and clicking the OK button after each setting. Setting Unit Configuration >

Filter Service Alarm Timer

value to 0 disables the filter service alarm function.

Airside Linkage Alarm

- An RTU Open may act as an air source in a zoned system. Carrier systems utilize a

function called Linkage™ to pass data between a master zone and its air source via an MS/TP network

connection. When the RTU Open is part of a linked system, it will indicate an airside linkage alarm if it loses

communications with its linkage master or if it receives invalid data.

Linkage

The RTU Open may serve as an air source to an Open Variable Volume Terminal (VVT) system. When the RTU

Open is part of a VVT system and the controllers are wired together to form a network, the controllers may use

a method of communication known as Linkage™. Linkage is a method by which an air source and its

subordinate zone terminals exchange data to form a coordinated HVAC system. The system's air source

controller, zone controllers, and bypass controller are linked so that their data exchange can be managed by

one zone controller configured as the VVT Master.
The VVT Master gathers the following information from the slave zone controllers:

occupancy status

setpoints