Appendix A: RTU Open Points/Properties
66
RTU Open
Effective Setpoints
The Effective Setpoints graph shows the current occupied or unoccupied setpoints. If occupied, these values are the current
programmed setpoints plus the offset of any setpoint adjustment that may be in effect. If unoccupied, the values are the
programmed unoccupied setpoints.
Point Name/Description
Default/Range
Heating –
(Occupied or Unoccupied, depending on mode) The current programmed Heating
setpoint adjusted by any offset that may be in effect.
R:
0 to 120°F
Cooling –
(Occupied or Unoccupied, depending on mode) The current programmed Cooling
setpoint adjusted by any offset that may be in effect.
R:
0 to 120°F
Optimal Start
– The number of hours prior to occupancy, at which the Optimal Start function
may begin to adjust the effective setpoints to achieve the occupied setpoints by the time
scheduled occupancy begins. Enter 0 to disable Optimal Start.
D:
R:
4 hr
0 to 4 hr
Occ Relative Humidity Setpoint
– The percentage of relative humidity in the space during
occupancy that will energize BO - 6 (Humidi-MiZer™).
D:
R:
60%rh
0 to Unoccupied
RH Control
Setpoint
Unocc Relative Humidity Setpoint
– The percentage of relative humidity in the space during the
unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™).
D:
R:
95%
30 to 100%
DCV Max Ctrl Setpoint
– The design difference between indoor and outdoor CO2 levels.
D:
R:
650ppm
0 to 9999 ppm
Power Exhaust Setpoint
- The outside air damper position at which the controller energizes the
Power Exhaust relay. Configuration >Service Configuration > Economizer Exists must be set to
Yes
, and Configuration >Service Configuration > Continuous Occupied Exhaust must be set to
No
.
D:
R:
50% Open
20 to 90% Open