RTU Open
69
Point Name/Description
Default/Range
System Space Temperature
– The network space temperature value that the
controller is using for control (if applicable).
D:
R:
-999.00 °F
N/A
System Cool Demand Level
– The system cool demand level being received over the
network.
D:
R:
0.00
0 - 3
System Heat Demand Level
– The system heat demand level being received over the
network.
D:
R:
0.00
0 - 3
System Outside Air Temperature
– Allows the outside air temperature value to be
network readable when enabled. Requires controller be equipped with an outdoor air
temperature sensor.
D:
R:
-999.0°F
N/A
Service Test
Service Test
– Enable to stop automatic control so you can test the controller's
outputs. Automatically resets to Disable after 1 hour.
D:
R:
Disable
Disable/Enable
Fan Test
– Enable to test the controller's fan speeds. Sequences fan from low to high
speed and operates at each speed for 1 minute. Resets to Disable when complete.
Service Test
must be set to Enable.
D:
R:
Disable
Disable/Enable
Compressor 1 Test
– Enable to test the controller's compressor 1 output. Service
Test
must be set to Enable.
D:
R:
Disable
Disable/Enable
Compressor 2 Test
– Enable to test the controller's compressor 2 output. Service
Test
must be set to Enable.
D:
R:
Disable
Disable/Enable
Heat 1 Test
– Enable to test the controller's heat 1 output. Service Test must be set
to Enable.
D:
R:
Disable
Disable/Enable
Heat 2 Test
– Enable to test the controller's heat 2 output. Service Test must be set
to Enable.
D:
R:
Disable
Disable/Enable
Reversing Valve Test
– Enable to test the controller's reversing valve output. Service
Test
must be set to Enable.
D:
R:
Disable
Disable/Enable
Dehumidification Test
– Enable to test the controller's humidimizer output. Service
Test
must be set to Enable.
D:
R:
Disable
Disable/Enable
Power Exhaust Test
– Enable to test the controller's exhaust fan output. Service Test
must be set to Enable.
D:
R:
Disable
Disable/Enable
Economizer Test
– Set to a value between 0 and 100% to test the controller's
economizer output. Service Test must be set to Enable.
D:
R:
0% Open
0 to 100% Open
Analog Output 2 Test
– Analog Output 2 (0-10 Vdc) is currently unused.
D:
R:
0%
0 to 100%