RTU Open

69

Point Name/Description

Default/Range

System Space Temperature

– The network space temperature value that the

controller is using for control (if applicable).

D:
R:

-999.00 °F
N/A

System Cool Demand Level

– The system cool demand level being received over the

network.

D:
R:

0.00
0 - 3

System Heat Demand Level

– The system heat demand level being received over the

network.

D:
R:

0.00
0 - 3

System Outside Air Temperature

– Allows the outside air temperature value to be

network readable when enabled. Requires controller be equipped with an outdoor air

temperature sensor.

D:
R:

-999.0°F
N/A

Service Test

Service Test

– Enable to stop automatic control so you can test the controller's

outputs. Automatically resets to Disable after 1 hour.

D:
R:

Disable
Disable/Enable

Fan Test

– Enable to test the controller's fan speeds. Sequences fan from low to high

speed and operates at each speed for 1 minute. Resets to Disable when complete.

Service Test

must be set to Enable.

D:
R:

Disable
Disable/Enable

Compressor 1 Test

– Enable to test the controller's compressor 1 output. Service

Test

must be set to Enable.

D:
R:

Disable
Disable/Enable

Compressor 2 Test

– Enable to test the controller's compressor 2 output. Service

Test

must be set to Enable.

D:
R:

Disable
Disable/Enable

Heat 1 Test

– Enable to test the controller's heat 1 output. Service Test must be set

to Enable.

D:
R:

Disable
Disable/Enable

Heat 2 Test

– Enable to test the controller's heat 2 output. Service Test must be set

to Enable.

D:
R:

Disable
Disable/Enable

Reversing Valve Test

– Enable to test the controller's reversing valve output. Service

Test

must be set to Enable.

D:
R:

Disable
Disable/Enable

Dehumidification Test

– Enable to test the controller's humidimizer output. Service

Test

must be set to Enable.

D:
R:

Disable
Disable/Enable

Power Exhaust Test

– Enable to test the controller's exhaust fan output. Service Test

must be set to Enable.

D:
R:

Disable
Disable/Enable

Economizer Test

– Set to a value between 0 and 100% to test the controller's

economizer output. Service Test must be set to Enable.

D:
R:

0% Open
0 to 100% Open

Analog Output 2 Test

– Analog Output 2 (0-10 Vdc) is currently unused.

D:
R:

0%
0 to 100%