Input wiring specifications – Carrier RTU OPEN 11-808-427-01 User Manual

Page 19

background image

RTU Open

13

Channel

Number

Type

Signal

Function

Part Number

Wire/Terminal

Numbers

Alternate

Terminals

BO - 2

BO

N/A - Relay

Heat 2 (W2) Output

N/A

J1

- 5

N/A

BO - 3

BO

N/A - Relay

Heat 1 (W1) Output

N/A

J1

- 6

N/A

BO - 4

BO

N/A - Relay

Cool 2 (Y2) Output

N/A

J1

- 7

N/A

BO - 5

BO

N/A - Relay

Cool 1 (Y1) Output

N/A

J1

- 8

N/A

BO - 6

BO

N/A - Relay

Humidi-MiZer™

N/A

J11

- 7 & 8

N/A

BO - 7

BO

N/A - Relay

Reversing Valve

N/A

J11

- 4 & 6

N/A

BO - 8

BO

N/A - Relay

Power Exhaust

N/A

J11

- 1 & 3

N/A

Legend

AI

- Analog Input

AO

- Analog Output

BI

- Digital Input

BO

- Digital Output


*

Safety Chain Feedback

- 24 Vac required at this wire to provide

Run Enabled

status. Provide a jumper from

J1

- 1 to

J1

- 9 if no

safeties are utilized. See To wire inputs and outputs (page 14) for additional information on the RTU Open wiring harness assembly

terminations.

** Default input function

*** Parallel screw terminal at

J5

(

J5

- 1 =

J2

- 6,

J5

- 3 =

J1

- 10,

J5

- 5 =

J1

- 2) may be used in place of the associated flying leads at

the harness (Part #OPN-RTUHRN). See To wire inputs and outputs (page 14) for additional information.


Input wiring specifications

Input

Maximum length

Minimum gauge

Shielding

Thermistor

1000 feet

(305 meters)

22 AWG

Unshielded

4-20 mA

3000 feet

(914 meters)

22 AWG

Unshielded

Binary input

1000 feet

(305 meters)

22 AWG

Unshielded

SPT (RNET)

500 feet

(152 meters)

22 AWG

4 conductor

Unshielded