RTU Open

71

Point Name/Description

Default/Range

BAS On/Off

– Determines the occupancy state of the controller and can be set over the

network by another device or third party BAS.
Options:

Inactive

– Occupancy is determined by a configured schedule.

Occupied

– The controller is always in the occupied mode.

Unoccupied

– The controller is always in the unoccupied mode.

NOTE

If BAS On/Off is set to either Unoccupied or Occupied, the Optimal Start routine is

automatically disabled.

D:
R:

Inactive
Inactive

Occupied

Unoccupied

Schedules

– The controller's occupancy status based on the local schedule.

R:

Occupied/Unoccupied

Pushbutton Override

– Active indicates if a user pushed the sensor's override button to

override the occupancy state.

R:

Off/Active

Override Time Remaining

– The amount of time remaining in an override period.

R:

0 to 240 minutes

Runtime

Supply Fan Runtime

– The total number of hours that the supply fan relay has been

energized since the runtime was last reset to 0 using Reset Supply Fan Runtime Alarm.

R:

___ hr

Compressor 1 Runtime

– The total number of hours that the Compressor 1 relay has

been energized since the runtime was last reset 0 using Reset Comp 1 Runtime Alarm.

R:

___ hr

Compressor 2 Runtime

– The total number of hours that the Compressor 2 relay has

been energized since the runtime was last reset using Reset Comp 2 Runtime Alarm.

R:

___ hr

Filter Runtime

– The total number of hours that the unit has been operating since the

runtime was last reset to 0 using Reset Filter Runtime Alarm.

R:

___ hr


Alarms

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Alarms

HOME > ALARM

Point Name/Description

Range

Safety Chain

– Indicates if the Safety Chain circuit trips.

R:

Normal/Alarm

Fire Shutdown

– Indicates if the Fire Shutdown circuit trips.

R:

Normal/Alarm

Compressor Safety

– Indicates if the Compressor Safety circuit trips.

R:

Normal/Alarm

Space Temp Sensor –

Indicates if the space temperature sensor fails.

R:

Normal/Alarm